MODGAS-XWR-1 Technical Guide
COMMUNICATING WIRING
17
Figure 14: Secondary Board 2V1IGN1S Communicating Wiring Diagram
Secondary Board 2V1IGN1S - Communicating Wiring
Secondary Board (2V1IGN1S) -
Communicating Wiring
In this confi guration, the Two Modulating Valves wiring on the facing
page is the Primary portion and
Figure 14, below
is the Secondary por-
tion, thus creating four modulating valves as one stage.
This confi guration operates as Stand-Alone (
Figure 6, page 9
) or
communicating with an AAON Unit Controller.
NOTE:
Up to 3 additional fi xed heat stages can be used by using
Heat Relays 3 & 4 below. If additional fi xed stages are
required, these should be confi gured and wired to the
AAON Unit Controller’s relays.
NOTE:
The Four Modulating Valves Primary/Secondary
configuration is not supported when using I
2