background image

                        OPERATION MODES & STAGING CONFIGURATIONS

19

         

         

MODGAS-XWR-1 Technical Guide

 

Operation Modes & Staging Con

fi

 gurations

Operation Modes

The MODGAS-XWR Controller can be used stand-alone or connected 
to a Main Controller using a modular cable (communicating).

Stand Alone Mode

When used in a stand-alone application (not connected to a Main Control-
ler via a modular cable), the MODGAS-XWR Controller will modulate 
the gas valve(s) to maintain the DISCHARGE setpoint confi gured on 
the  MODGAS-XWR  Controller  LCD  display. The  MODGAS-XWR 
Controller is activated by a 24VAC signal to the HEAT EN input.

The following describes the setpoints available in stand-alone mode for 
adjustment using the LCD display on the MODGAS-XWR Controller: 

• 

Supply Air Temperature Setpoint

 

• 

Supply Air Reset Temperature Setpoint 

Communicating Mode

When the MODGAS-XWR Controller is connected to a Main Controller 
via a modular cable, the necessary information will be passed between 
the MODGAS-XWR and the Main Controller to properly operate in 
the Heating Mode.

If the communication is interrupted between the MODGAS-XWR Con-
troller and the Main Controller, both boards will show an alarm. When 
communication is restored, the alarms will go away.

In this confi guration, the Supply Air Temperature Setpoint is set using 
the Main Controller and the Supply Air Temperature Reset (if used) is 
calculated by the Main Controller. The Supply Air Temperature is sent 
to the MODGAS-XWR from the Main Controller.

MODGAS-XWR Staging Con

fi

 gurations

The MODGAS-XWR can be confi gured for various Staged Heat con-
fi gurations. These confi gurations can be used in conjunction with the 
VCM-X E-BUS Controller, VCB-X Controller, VCCX2 Controller, or 

12 Relay E-BUS Expansion Module

.  

MODGAS-XWR Stand-Alone Con

fi

 guration

The fi rst and second confi guration screens designate the Primary and 
Secondary boards if using two MODGAS-XWR-1’s.

The third confi guration screen allows selection of Stand-Alone Auto 
(no 12 Relay board) or Stand-Alone Forced (using the 12 Relay board). 

The fourth confi guration screen allows selection of the Total Stages, 
which is the number of Heat Stages installed in the unit (note that if there 
are two heat units to be operated in a primary/secondary arrangement, 
this is considered 1 stage of heat). 

The  fi fth  confi guration  screen  selects  the  confi guration. The  options 
for Stand-Alone operation are (1) 1 modulating, 1 ignitor, 1 stage, (2) 
2 modulating, 2 ignitors, 1 stage, (3) 2 modulating, 2 ignitors, 2 stages 
(which allows a secondary MODGAS-XWR-1), and (4) 2 modulating, 
1 ignitor, 1 stage (which allows a secondary MODGAS-XWR-1).

MODGAS-XWR Stand-Alone with 12-Relay 

E-BUS Expansion Module

In order for the MODGAS-XWR to communicate properly to the 12 
Relay  Expansion  Module,  “S/A  MODE”  needs  to  be  confi gured  to 
“FORCED”. This confi guration will make the MODGAS-XWR initi-
ate communications with the 12 Relay Expansion Module through the 
E-BUS cable.

MODGAS-XWR Communicating with AAON 

Unit Controller

The fi rst and second confi guration screens designate the Primary and 
Secondary boards if using two MODGAS-XWR-1’s.

The fourth confi guration screen allows selection of the Total Stages, 
which is the number of Heat Stages installed in the unit (note that if there 
are two heat units to be operated in a primary/secondary arrangement, 
this is considered 1 stage of heat). 

If more stages of heat are needed besides the MODGAS-XWR and the 
main control board’s confi gurable relays, a 12 Relay E-BUS Expansion 
Module or an additional expansion board can be connected to the Main 
Controller and heat stages can be confi gured for the 12 Relay board from 
the Main Controller. If using the 12 Relay board, the third confi guration 
screen must be set at Stand-Alone Forced.

The  fi fth  confi guration  screen  selects  the  confi guration. The  options 
for Stand-Alone operation are (1) 1 modulating, 1 ignitor, 1 stage, (2) 
2 modulating, 2 ignitors, 1 stage, (3) 2 modulating, 2 ignitors, 2 stages 
(which allows a secondary MODGAS-XWR-1), and (4) 2 modulating, 
1 ignitor, 1 stage (which allows a secondary MODGAS-XWR-1).

NOTE: 

 The Primary/Secondary confi guration is not supported 

when using the VCM-X E-BUS Controller.

The status screen displaying the stage status will show the current heat 
stage of all heat stages on the unit. For example, if two stages are active 
on the MODGAS-XWR and two stages are active on the main control 
board, the current heat stage displayed will show HEAT STAGE 4.

Summary of Contents for OE377-26-00060-1

Page 1: ...OE377 26 00060 1 AAON Part No V82790 MODGAS XWR Controller Technical Guide Factory Packaged Controls ...

Page 2: ...PLAY SCREENS 22 TROUBLESHOOTING 29 APPENDIX A Supply Air Temperature Sensor Guide 34 APPENDIX B MODGAS XWR 1 Replacement of MODGAS XWR 36 PART DESCRIPTION PART NUMBER MODGAS XWR 1 Controller V82790 MODGAS XWR Controller V20780 VCCX2 Controller V87900 VCB X Controller V28940 VCM X Modular E BUS Controller V07150 12 Relay E BUS Expansion Module R69180 Supply Air Temperature Sensor P87140 AAON Inc 24...

Page 3: ...The controller can be used as a stand alone unit or be connected to a 12 Relay E BUS Expansion Module stand alone only or VCM X E BUS I2 C Controller VCB X Controller or VCCX2 Controller using a modular cable The MODGAS XWR Controller can be configured for one 1 modulat ing valve with one ignitor as one stage two 2 modulating valves with one ignitor as one stage two 2 modulating valves with two ign...

Page 4: ...at all ground wires remain common Failure to follow this procedure can result in damage to the module and connected devices 5 All wiring is to be in accordance with local and national electrical codes and specifications 6 Check all wiring leads at the terminal block for tightness Be sure that wire strands do not stick out and touch adjacent terminals Confirm that all transducers required for your sy...

Page 5: ...AAON Unit Controller Figure 9 page 12 This configuration is used to control one modulating valve which must be placed on the gas valve 1 header attached to Heat 1 Relay NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 2 3 4 below and up to 12 more additional fixed stages can be added by using the 12 Relay E BUS Expansion Module Figure 8 page 11 If using an MHGRV X Controller...

Page 6: ... modulating gas valves one on each header in which the first valve is modulating stage 1 valve 1 header and the second valve is modulating stage 2 valve 2 header The first valve is attached to Heat Relay 1 and the second valve is at tached to Heat Relay 2 NOTE Up to 2 additional fixed heat stages can be used by using Heat Relays 3 4 below and up to 12 more additional fixed stages can be added by using...

Page 7: ... tion thus creating four modulating valves as 2 stages This configuration operates as Stand Alone Figure 4 below or communicating with an AAON Unit Controller Figure 12 page 15 NOTE Up to 2 additional fixed heat stages can be used by using Heat Relays 3 4 below and up to 12 more additional fixed stages can be added by using the 12 Relay E BUS Expansion Module Figure 8 page 11 If using a MHGRV X Cont...

Page 8: ...ach header in which the first and second valves operate together for one modulating stage Both valves are connected to Heat 1 Relay NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 2 3 4 below and up to 12 more additional fixed stages can be added by using the 12 Relay E BUS Expansion Module Figure 8 page 11 If using an MHGRV X Controller along with the MODGAS XWR Controller...

Page 9: ...ion thus creating four modulating valves as one stage This configuration operates as Stand Alone Figure 6 below or communicating with an AAON Unit Controller Figure 14 page 17 NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 2 3 4 below and up to 12 more additional fixed stages can be added by using the 12 Relay E BUS Expansion Module Figure 8 page 11 If using a MHGRV X Con...

Page 10: ...is used to control two modulating gas valves one on each header in which the first and second valves operate together for one modulating stage One valve is connected to Heat 1 Relay and the second valve is connected to Heat 2 Relay NOTE Up to 2 additional fixed heat stages can be used by using Heat Relays 3 4 below and up to 12 more additional fixed stages can be added by using the 12 Relay E BUS Exp...

Page 11: ...he 12 Relay E BUS Expansion Module to operate the Stand Alone setting in the LCD Configuration Screens must be set to Forced If communication is lost to the 12 Relay E BUS Expansion Module the 12 Relay E BUS Expansion Module will turn off its relays and the MODGAS XWR Controller will alarm and fall back to using only its onboard stages If communications is restored the MODGAS XWR Controller will beg...

Page 12: ...valve 1 header attached to Heat 1 Relay For VCM X Controllers use an I2 C Cable connecting to the appropriate I2 C port on the controller For all other controllers use an E BUS cable connecting to an E BUS port on the controller NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 2 3 4 below If additional fixed stages are required these should be configured and wired to the AAO...

Page 13: ...ating stage One valve is connected to Heat 1 Relay and the second valve is connected to Heat 2 Relay For VCM X Controllers use an I2 C Cable connecting to the appropriate I2 C port on the controller For all other controllers use an E BUS cable connecting to an E BUS port on the controller NOTE Up to 2 additional fixed heat stages can be used by using Heat Relays 3 4 below If additional fixed stages ...

Page 14: ...one on each header in which the first valve is modulating stage 1 valve 1 header and the second valve is modulating stage 2 valve 2 header The first valve is attached to Heat Relay 1 and the second valve is at tached to Heat Relay 2 For VCM X Controllers use an I2 C Cable connecting to the appropriate I2 C port on the controller For all other controllers use an E BUS cable connecting to an E BUS por...

Page 15: ...nd Figure 12 below is the Secondary por tion thus creating four modulating valves as two stages This configuration operates as Stand Alone Figure 4 page 7 or communicating with an AAON Unit Controller NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 3 4 below If additional fixed stages are required these should be configured and wired to the AAON Unit Controller s relays NOTE...

Page 16: ...ng gas valves one on each header in which the first and second valves operate together for one modulating stage Both valves are connected to Heat 1 Relay NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 2 3 4 below If additional fixed stages are required these should be configured and wired to the AAON Unit Controller s relays For VCM X Controllers use an I2 C Cable connectin...

Page 17: ...and Figure 14 below is the Secondary por tion thus creating four modulating valves as one stage This configuration operates as Stand Alone Figure 6 page 9 or communicating with an AAON Unit Controller NOTE Up to 3 additional fixed heat stages can be used by using Heat Relays 3 4 below If additional fixed stages are required these should be configured and wired to the AAON Unit Controller s relays NOTE...

Page 18: ...f Flame alarm Proof of Ignition 2 PO IGN2 The Proof of Ignition input is activated by a 24VAC signal supplied from the Ignition Module to enable the modulating Gas Valve 2 If the flame does not ignite the Ignition Module will turn off this enable The MODGAS XWR Controller will then turn on the No Proof of Flame alarm Communicating Outputs Gas Valve Output 1 This communicating output will control the...

Page 19: ...mber of Heat Stages installed in the unit note that if there are two heat units to be operated in a primary secondary arrangement this is considered 1 stage of heat The fifth configuration screen selects the configuration The options for Stand Alone operation are 1 1 modulating 1 ignitor 1 stage 2 2 modulating 2 ignitors 1 stage 3 2 modulating 2 ignitors 2 stages which allows a secondary MODGAS XWR 1...

Page 20: ... speed 2V2IGN2S The PID loop runs every 10 seconds and determines the modulation percentage for the one variable valve Then the valve moves to the correct position Only after the stage up delay requirement has been met will the board stage up and open the second variable valve After this both valves will move simultaneously to the same percent modulations During the modulation sequence if the valv...

Page 21: ...but keep in mind that bringing one below the low speed cutoff and another above it will cause low speed relay difficulties Forcing stages 2 4 on forces Heat Relays 2 4 on respectively 2V1IGN1S Forcing stage 1 on forces Heat Relay 1 on and the next screen allows the option to select the modulation percentage since both valves are one stage they both modulate at the same percentage Forcing stages 2 4 o...

Page 22: ...to turn Valve Force Mode off ENTER Use the Enter key to move through screens within Main Menu categories Also use this key to save setpoints and configuration changes Main Screens Map Refer to the following map when navigating through the LCD Main Screens The first screen is an initialization screen To scroll through the rest of the screens press the MENU button MGAS XWR 1086vXXX STATUS MENU ALARMS M...

Page 23: ...is a loss of communication for either E BUS master or slave or I2C the Controller moves into this mode This state re initializes communications and then puts the Controller into COMM_RECOVER mode Normal board operations do not continue when in this mode e g you cannot go into Heat mode COMM_RECOVER After the Controller moves into COMM_TIME OUT the Controller is then put into this mode The Controll...

Page 24: ...he Controller is being tested for the VCM X via I2C communications then the Controller moves into this mode MOD HEAT STAGE After Ignition Mode the unit will enter the Heat Mode and will begin to modulate the gas valve s to maintain the Heating Supply Air Setpoint SAT Once the call for heat goes away the unit will leave the Heat Mode SLAVE_HEATING If the Controller is a Modbus slave to another MODG...

Page 25: ...t Screens From the SETPOINT Screen press ENTER to scroll through the screens and change setpoints Use the UP and DOWN arrow keys to change your selections Then press ENTER to save the new setpoint WARNING The ENTER key must be pressed after changing setpoints for your entries to be saved for subsequent power ups NOTE When the MODGAS XWR is operating in Communi cations Mode these setpoints screens ...

Page 26: ...the Force Mode back off or after 10 minutes of no keypad input the valve will go to zero and the relays will turn off STAGE 2 FORCE ON OFF DISABLED V2 POSITION X FORCE VALVE 2 PERCENTAGE This screen only appears when Valve 2 Force is on Press the UP button to turn the Force Mode on Press the DOWN button to turn the Force Mode off If the screen says disabled on off selection is not possible Press the U...

Page 27: ...d to Heat 1 Relay Additional stages may be added to Heat Relays 2 3 4 or off board if in a communication mode 2V1IGN1S Valve configuration used to control two modulating gas valves one on each header in which the first and second valves operate together for one modulating stage Both valves are connected to Heat 1 Relay therefore an additional fixed stage may be added on board at the Heat 2 Relay Addit...

Page 28: ...steps Default is 70 STG UP DLY 1 TO 10 m STAGE UP DELAY Range is 1 to 10 minutes Default is 3 IGN RTRY DLY 1 60 m IGNITION RETRY DELAY Range is 1 60 minutes Default is 30 STG DOWN DLY 1 TO 10 m STAGE DOWN DELAY Range is 1 or 10 minutes Default is 1 LOSAT SU 0 45 F LOW SUPPLY AIR TEMPERATURE START UP Range is 0 45ºF Default is 40ºF If the Supply Air Temperature is 40 adjustable or less the stage up...

Page 29: ... Failure 10 Stage 2 Failure Table 4 ALARM LED Blink Codes Communication LED COMM This yellow LED will light up and blink when communications are detected If this LED never blinks then there is no communication Relay LEDs RLY1 This green LED will light up and stay lit as long as the Fan relay is active RLY2 This green LED will light up and stay lit as long as the Low Speed Fan relay is active RLY3 ...

Page 30: ...TROUBLESHOOTING MODGAS XWR 1 Technical Guide 30 Figure 16 MODGAS XWR Controller LED Locations and Descriptions Troubleshooting ...

Page 31: ...GND on the Main Controller communicating mode Remove SAT and GND wiring from MODGAS XWR and ohm sensor out this may indicate open or failed wiring Refer to chart on pages 30 31 of this guide for readings Verify the SAT OPTIONS jumper settings on the MODGAS XWR for the Supply Air Temperature Sensor Fail Mode SAT Cutoff Remove SAT and GND wiring from the MODGAS XWR and ohm sensor out this may indica...

Page 32: ... 0 60552 2 83 10 12 2 52500 2 77 15 9 4 45902 2 71 20 6 7 40147 2 64 25 3 9 35165 2 57 30 1 1 30805 2 49 35 1 6 27140 2 41 40 4 4 23874 2 33 45 7 2 21094 2 24 50 10 0 18655 2 15 52 11 1 17799 2 11 54 12 2 16956 2 08 56 13 3 16164 2 04 58 14 4 15385 2 00 60 15 6 14681 1 96 62 16 7 14014 1 93 64 17 8 13382 1 89 66 18 9 12758 1 85 Temperature to Resistance Voltage Chart Temp F Temp C Resistance Ohms ...

Page 33: ... 40147 4 095 25 3 9 35165 3 982 30 1 1 30805 3 862 35 1 6 27140 3 737 40 4 4 23874 3 605 45 7 2 21094 3 470 50 10 0 18655 3 330 52 11 1 17799 3 275 54 12 2 16956 3 217 56 13 3 16164 3 160 58 14 4 15385 3 100 60 15 6 14681 3 042 62 16 7 14014 2 985 64 17 8 13382 2 927 66 18 9 12758 2 867 68 20 0 12191 2 810 69 20 6 11906 2 780 70 21 1 11652 2 752 71 21 7 11379 2 722 72 22 2 11136 2 695 73 22 7 1087...

Page 34: ... to these instructions prior to testing the unit or else the modulating valve will not control properly and may damage your equipment Figure 17 Supply Air Temperature Sensor Installation Stand Alone Mode In Stand Alone Mode the SATSensor is connected to the MODGAS X Controller If in Stand Alone Mode the MODGAS X Controller is used in conjunction with a Stand Alone MHGRV Controller the SAT sensor i...

Page 35: ...r VCCX2 Connect to VCB X or VCCX2 using E BUS cable Install Supply Air Sensor in VCB X or VCCX2 Connect to VCB X or VCCX2 using E BUS cable VCM X SA RNE Install Supply Air Sensor in Main Controller Connect to Main Controller using I2 C cable Install Supply Air Sensor in Main Controller Connect to Main Controller using I2 C cable VCM VAV CAV MUA MUA II MUA IID Install Supply Air Sensor in MODGAS XW...

Page 36: ...rature Sensor needs to remain installed on whatever controller it is currently on Figure 18 MODGAS XWR 1 Controller Step 4 Unplug the TB2 Input Terminal Block from the MODGAS XWR and replug it into the MODGAS XWR 1 board Step 5 Unplug the Ignition blocks and Valve headers from the MODGAS XWR and replug them into the MODGAS XWR 1 board Step 6 Wire the MODGAS XWR 1 relays according to the valve confi...

Page 37: ...MODGAS XWR 1 Technical Guide NOTES 37 ...

Page 38: ...NOTES MODGAS XWR 1 Technical Guide 38 ...

Page 39: ...MODGAS XWR 1 Technical Guide NOTES 39 ...

Page 40: ...2425 South Yukon Ave Tulsa OK 74107 2728 Ph 918 583 2266 Fax 918 583 6094 AAON Part No V73440 Rev 01B Printed in the USA November 2018 AAON All Rights Reserved ...

Reviews: