WIRING OVERVIEW & MODULE DIMENSIONS
MODGAS-XWR-1 Technical Guide
4
Important Wiring Considerations & Module Dimensions
Important Wiring Considerations
Please read carefully and apply the following information when wir-
ing the
MODGAS-XWR
Controller.
The MODGAS-XWR Controller
requires the following electrical connections:
1.
18 gauge minimum wire unless otherwise noted
2.
24 VAC power connection with an appropriate VA rating
3. Supply Air Temperature Sensor and Heat Enable must have
24 gauge minimum wire
4. All 24 VAC wiring must be connected so that all ground
wires remain common. Failure to follow this procedure can
result in damage to the module and connected devices
5. All wiring is to be in accordance with local and
national electrical codes and specifi cations
6. Check all wiring leads at the terminal block for tightness.
Be sure that wire strands do not stick out and touch
adjacent terminals. Confi rm that all transducers required for
your system are mounted in the appropriate location and
wired into the correct terminals
WARNING:
Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-24 VAC.
Failure to observe polarity could result in
damage to the board.
WARNING:
Attach all valves to header before supplying
power to the board.
Figure 1: MODGAS-XWR-1 Controller Dimensions (in inches)