52
To lower the pressure set point for the
CUT
IN
gauge, turn the adjustable screw
clockwise.
To raise the pressure set point for the
CUT IN
gauge, turn the adjustable screw counter
clockwise.
To raise the pressure set point for the
DIFFERENTIAL
Gauge, turn the adjustable
screw clockwise.
To lower the pressure set point for the
DIFFERENTIAL
Gauge, turn the adjustable
screw counter clockwise.
NOTE: The pressure values on the gauge must be verified with gauges on the refrigerant line.
The gauge scale is for illustration purposes only.
Cut In Gauge
Cut In Gauge
Differential
Gauge
Differential
Gauge