29
determining if vent gases may degrade
building materials.
The National Gas and Propane Installation
Code, B149.1 specifies a 6 ft. horizontal vent
terminal clearance to gas and electric meters
and relief devices.
Local codes may supersede or further place
restrictions on vent termination locations.
Table 1 - Air-Cooled Condenser Unit
Clearances 45-240 ton
Location
Clearance for
45-240 ton units
Front (
Condenser Side
)
60”
Back (
Outside Air
)
100”
Left
100”
Right
100”
Top
Unobstructed
Figure 2 - RZ Series Unit Orientation
Table 2 - Evaporative Condenser Unit
Clearances 45-240 ton
Location
Clearance for
45-240 ton units
Front (
Condenser Side
)
100”
Back (
Outside Air
)
100”
Left
100”
Right
100”
Top
Unobstructed
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate area
around the condenser must remain free of
debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb Installation
Make openings in the roof decking large
enough to allow for duct penetrations and
workspace only. Do not make openings
larger than necessary. Set the curb to coincide
with the openings. Make sure curb is level.
Unit must be level in both horizontal axes to
support the unit and reduce noise and
vibration.
Unit specific curb drawing is included with
job submittal. See SMACNA
Architectural
Sheet Metal Manual
and
HVAC Duct
Construction Standards
for curb installation
details.
All roofing work must be performed by
competent roofing contractors to
avoid any possible leakage.
CAUTION
Where the supply or warm air duct
passes through a combustible roof, a
clearance
of 1 inch must be
maintained
between
the outside
edges of the duct and combustible
material in accordance with National
Fire Protection Association Standard
No.
90A.
Provide
flashings
or
enclosure between structure and roof
and all joints must be sealed with
mastic roofing to ensure a watertight
seal.