Chilled Water Coil
Four, six, or eight row chilled water cooling coils can be factory installed. All valve controls for
cooling operation are field supplied and field installed. Chilled water coil connections are spun
copper tube.
Table 16 - Chilled Water Coil Connection Sizes
Model (RZA-)
Chilled Water Coil
Connection Size
Coil Quantity*
045, 055, 065, 075, 090, 105,
120, 130, 140
2 5/8”
4/4
145, 160, 180, 200, 220, 240
2 5/8”
8/8
* In/Out Connections
Packaged Direct Expansion (DX) Units
All DX refrigeration systems are factory
assembled,
leak tested, charged with
refrigerant, and run tested.
All refrigerant systems include evaporator
and condenser coils. Each unit includes
replaceable core liquid line filter driers,
replaceable
suction
filters,
compressor
isolation valves, electronic expansion valves,
and variable speed scroll compressors.
Never turn off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit, crankcase heaters
cannot prevent refrigerant migration into the
compressors. This means the compressor
may cool down and liquid refrigerant may
accumulate
in
the
compressor.
The
compressor is designed to pump refrigerant
gas and damage may occur when power is
restored if liquid enters the compressor.
If power to the unit must be off for more than
an hour, turn the unit off at the control panel,
and leave the unit off until the main power
switch has been turned on again for at least
24 hours for units with compressor crankcase
heaters. This will give the crankcase heater
CRANKCASE HEATER
OPERATION
Some units are equipped
with
compressor crankcase heaters, which
must be energized at least 24 hours
prior to cooling operation, to clear any
liquid
refrigerant
from
the
compressors.
CAUTION
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 3 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 7
starts per hour.
WARNING