Evaporative Condenser Location
The recirculating water system contains
chemical additives for water quality control
and biological contaminants removed from
the air by the washing action of the water.
Personnel exposed to the saturated effluent,
drift, or direct contact must use proper
precaution.
Proper
location
of
the
evaporative
condenser
requires
good
judgment to prevent the air discharge from
entering fresh air intakes or to avoid allowing
contaminated building exhaust from entering
the condenser.
Figure 28 - Proper Unit Location
Follow local and national codes in locating
the evaporative condenser but as minimum
the evaporative condenser sump must be 15
feet from the nearest intake.
Figure 29 - Improper Unit Locations
Performance
Improper
location
of the evaporative
condenser may seriously
degrade the
capacity of the equipment. Make sure the
equipment is located such that discharge air
from the condenser does not enter the
condenser air inlet.
Batch-loading chemicals into the unit
is NOT PERMITTED. The control
system must regulate the chemical
feed.
WARNING
The evaporative condenser must be
thoroughly cleaned on a regular basis
to minimize the growth of bacteria,
including Legionella Pneumophila, to
avoid the risk of sickness or death.
Service personnel must wear proper
personal protective equipment. Do
not attempt any service unless the fan
motor is locked out.