72
1.
Monolith energy recovery wheel
2.
Purge Sector
3.
Profile
4.
Motor
5.
Brush Plate
6.
Rotor Hub
7.
Casing
Aluminum Wheel Check Purge Location
The purge sector is an optional element so it
may not be installed on some units. Ensure
the purge sector is mounted in the correct
location. Purge sector must be located on the
fresh supply air side. Based on the airflow
and the wheel rotation in the following
illustrations, notice the correct locations for
the purge sector.
Figure 34 - Aluminum ERW Purge
Sector Location
Aluminum Wheel Air Seals
Both
non-contact
sealing
on
wheel
peripheries and brush sealing middle beam
are maintenance-free but their condition must
be checked every year. During the inspection,
check their tightness and overall visual
condition. Non-contact seals must not be
flipped, rolled or pierced at any place
If seals are damaged, please contact our
technical support immediately. A damaged
seal may cause efficiency deterioration,
mixing of an air flows and unwanted leakages
in the system, especially in environments
with hygienic requirements.
Summary of Contents for RZ Series
Page 2: ......
Page 31: ...31 Figure 4 4 Point Lift RZ Series Air Cooled Condenser Unit ...
Page 90: ...90 Gas Heater Operating Instructions ...
Page 108: ...108 Maintenance Log E Coated Coil ...
Page 110: ...110 ...
Page 111: ......