Gas or Electric Heating
The unit is designed to heat a given airflow.
If this amount of air is greatly reduced,
approximately 1/3 during the heating season,
the gas heat exchanger or electric heating coil
may overheat, and may turn the burner or
heater off entirely by action of the safety high
temperature limit devices which are factory
mounted at the heat exchanger and supply
blower areas.
Adjust airflow after installation to obtain an
air temperature rise within the range
specified on the unit rating plate at the
required external static pressure.
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
If unit has not been selected as a 100%
outside air unit (makeup air unit) the return
air duct must be sealed to the unit and the
return air temperature must be maintained
between 55
F and 80
F.
Table 18 - RZ 45-140 ton Electric Heating Capacities
Model
Option B3
Electric Heat
Capacity
kW
(208V)
kW (230V,
380V 460V,
575V)
1
=
Heat 1
60.1
80
2
=
Heat 2
90.1
120
3
=
Heat 3
120.1
160
4
=
Heat 4
150.2
200
5
=
Heat 5
180.2
240
Table 19 - RZ 145-240 ton Electric Heating
Capacities
Model
Option B3
Electric Heat
Capacity
kW
(208V)
kW (230V,
380V 460V,
575V)
1
=
Heat 1
60.1
80
2
=
Heat 2
90.1
120
3
=
Heat 3
120.1
160
4
=
Heat 4
180.2
240
5
=
Heat 5
240.3
320
6
=
Heat 6
300.4
400
7
=
Heat 7
360.5
480
Table 20 - RZ 45-140 ton Gas Heating Capacities
Model
Option B3
Gas Heat
Capacity
Input
(MBH)
Output
(MBH)
1
=
Heat 1
540
437
2
=
Heat 2
810
656
3
=
Heat 3
1080
875
4
=
Heat 4
1350
1094
5
=
Heat 5
1620
1312
6
=
Heat 6
2100
1701
7
=
Heat 7
2580
2090
8
=
Heat 8
3060
2479
Table 21 - RZ 145-240 ton Gas Heating Capacities
Model
Option B3
Gas Heat
Capacity
Input
(MBH)
Output
(MBH)
1
=
Heat 1
800
648
2
=
Heat 2
1200
972
3
=
Heat 3
1600
1296
4
=
Heat 4
2000
1620
5
=
Heat 5
2400
1944
6
=
Heat 6
3100
2511
7
=
Heat 7
3800
3078
8
=
Heat 8
4500
3645