background image

WATER CONNECTIONS

Heating systems

The size of the heating system which can be run,
will depend on the output rating of the appliance. 
It will be necessary to work out heat loss
calculations for the system proposed in order to
establish the kW/hr rating. An appliance that will
meet this figure can then be chosen; (for boiler
outputs please refer to the brochure).

The constructional requirements of installing and
connecting the appliance also need to be taken into
account when selecting. Design and calculations
for individual heating systems should be carried out
by a qualified heating engineer. In many cases your
supplier will be able to offer advice and assistance.

Direct Systems

Stainless steel boilers, either factory fitted or
retro-fitted as add-in boilers enable connection to
direct systems to be made without the need to
change the cylinder or to fit an expansion tank. 
This applies to domestic water supply only 

and

should not be done when in an area with soft
water.

If radiators are used then an indirect system must be
utilised.
To connect the cylinder use 28mm copper pipes.
Ensure that the pipes rise continuously to the
cylinder.

Ensure that the runs are not too long, i.e. 20ft
maximum each for flow and return. Install the
cylinder above the level of the fire, and as close to
it as possible. (the higher the cylinder the faster the
circulation). Ensure that no valves are present in the
circulating pipes.

Indirect Systems - The Domestic Hot Water
Circuit

In addition to providing hot water the primary
circuit is essential in providing a "heat leak" to
absorb excessive heat produced in the event of the
circulation pump shutting down.

Heat is produced in varying quantities while the
fire is alight and care must be taken to ensure that

effective circulation can occur around the primary
circuit to carry heat away and thus stop boiling.

The output of any radiator installed as a "heat leak"
should not be less than 10% of the rated output of
the appliance. The radiator should 

not

be fitted

with a control valve.
The cylinder must be of the indirect type with a
minimum capacity of 110 litres, conforming to
BS 1566 part 1.
Primary flow and return pipes should be 28mm
diameter. The cylinder should be installed at a
higher level than the appliance, and as close to it as
possible (the higher the cylinder the faster the
circulation). The flow and return pipes should not
be longer than 20ft each. Pipe runs should rise
continually from the boiler to the cylinder. 
A radiator of approximately 25 sq.ft. should be
connected into the primary circuit, if installed in the
bathroom it provides a means of drying towels in
the summer.

Safety Vent Circuit

This circuit consists of a cold feed pipe, expansion
pipe, and expansion tank. The possibility that water
may boil can never be completely ruled out, and it
is therefore vital to ensure that cold water can be
supplied to the boiler and steam vented from it at all
times.

The expansion tank should have a capacity of at
least 7 % of the system's water capacity. The cold
water feed pipe should be at least 22mm diameter.

There must not be any shut off valves in the circuit.
Pipes should be run to avoid air locks. A safety
relief valve should be fitted to the expansion pipe
close to the boiler.

It is often possible, and is good practice, to utilise
the primary flow and return as part of the safety
circuit. The ball valve should have a copper ball.
The overflow pipe from the expansion tank should
be 28mm diameter copper. Pipes in unheated
spaces must be lagged.

28

Stratford Tf & Ti Multifuel Boiler Stoves

INSTALLATION

Summary of Contents for Stratford Tf

Page 1: ...n Tel 44 01308 427234 Fax 44 01308 427441 www aarrowfires com Operating Installation Manual PLEASE RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Rev 5 June 2004 Part No AFS1121 Stratford Tf 70 Boiler...

Page 2: ...which is why we are so confident in the reliability of our product Should you have any questions about our Stratford Stoves that are not covered in this manual please contact the Aarrow dealer in your...

Page 3: ...ce 14 Page INSTALLATION General Precautions 15 Combustible Materials 15 Multifuel Grate Grate Bars 16 Throat Plate Inspection 16 Flue Outlet and Hotplate 17 Flues and Chimneys 17 18 Integral Boilers 1...

Page 4: ...N THIS APPLIANCE TO USE THESE FUELS WILL INVALIDATE THE APPLIANCE GUARANTEE IF IN DOUBT CONTACT THE SOLID FUEL ASSOCIATION TELEPHONE NUMBER 0800 600 000 www solidfuel co uk THE USE OF SPARE PARTS OTHE...

Page 5: ...ot properly installed and operated a house fire may result Installation must comply with the Building Regulations and conform to all relevant fire safety standards Aarrow Fires produce a variety of ap...

Page 6: ...l Aid not to scale Stratford Tf 30b Stratford Tf 50b Stratford Tf 70b Stratford Tf 90b 2 Grate bars 5 7 9 9 3 Throat plate 1 1 1 1 4 Flue spigot 1 5 1 5 1 6 1 6 5 Hot plate 1 5 1 5 1 6 1 6 6 Ash pan 1...

Page 7: ...8 to 10 12 to 14 17 to 19 Height mm 596 645 709 709 Width mm 562 670 780 780 Depth mm 389 389 486 546 Height to centre of rear flue 447 503 555 555 Depth from back to centre of flue 138 138 172 172 F...

Page 8: ...nderdraught completely causing the fire to die down and in time go out to 8 fully clockwise the highest setting at which the appliance will burn fiercely and produce very high outputs For more informa...

Page 9: ...he grate in the coal burning position or the wood burning position This means that effective de ashing takes place and also allows the grate to be set in the coal burning or wood burning position as i...

Page 10: ...re door up off the hinges Gently tap the two hinge pins in a direction to compensate for the misalignment fig 7 Fig 7 Refit the door and check to ensure it now sits square to the body if not repeat ab...

Page 11: ...llowing fuels in this appliance Phurnacite Phurnacite Plus Centurion Maxibrite Extracite Pureheat Blazebrite Taybrite Sunbrite Doubles Singles Anthracite Large Nuts and Welsh Dry Steam Coal Large Smal...

Page 12: ...e that the area is well ventilated during this time OVERNIGHT BURNING The appliance will burn overnight provided Sufficient fuel is placed in the firebox The controls are set correctly Excess draught...

Page 13: ...prolonged periods may result in over firing If the chimney connector or casing glows red it is being over fired If this occurs immediately close all air inlets to the appliance to reduce the air suppl...

Page 14: ...is important that the flue ways flue pipe and chimney be cleaned prior to lighting the fire after a prolonged shut down period DOOR GLASS The door glass should remain clear during normal daytime burn...

Page 15: ...bustible materials not less than 125mm 5 thick conforming to Building Regulations Dimensions of the hearth should project at least 300mm 12 forward of the front of the appliance and 150mm 6 at the sid...

Page 16: ...e the operating tool behind the downstand tab marked throat plate and pull the plate frontward until its forward lugs drop into the cut away at the front of the side panel Check the upper surface for...

Page 17: ...aught it is important that the flue gases are kept warm and that the flue size suits the stove The termination of the outlet at the top of the flue also needs to comply with the Building Regulations T...

Page 18: ...tion requirements in respect of providing a Notice Plate giving details on the chimney flue lining hearth and fireplace installation Approved Document J of the Building Regulations for England and Wal...

Page 19: ...D CORRECTLY SET AT MANUFACTURE SO THE FOLLOWING PROCEDURES WILL ONLY BE REQUIRED WHEN REPLACING OR RE SETTING THE THERMOSTAT To fit remove thermostat on Tf models For fitting removal of thermostat on...

Page 20: ...f the thermostat before installing and running the appliance This is best seen from inside the appliance with the grate fuel retainer bars ash pan etc removed With the control set at minimum the dampe...

Page 21: ...Stratford Tf Ti Multifuel Boiler Stoves 21 INSTALLATION...

Page 22: ...ltifuel Stoves INSTALLATION PLAN VIEW OF REGISTER PLATE AND CLEARANCES FOR NON INSULATED FLUES A is minimum clearance for non insulated flue 1 5 x D to a non combustible surface material or 3 x D to c...

Page 23: ...Domestic Hot Water System Using Four Boiler Tappings Central Heating System Without Domestic Hot Water Using Four Boiler Tappings Note Diagrammatic representation only Design and calculations for indi...

Page 24: ...ystem Without Domestic Hot Water Using Three Tappings Note Diagrammatic representation only Design and calculations for individual systems should always be carried out by a qualified heating engineer...

Page 25: ...Stratford Tf Ti Multifuel Boiler Stoves 25 BOILER TAPPING POSITIONS Stratford Tf30 Boiler Tapping Positions Stratford Tf50 Boiler Tapping Positions All dimensions in mm...

Page 26: ...26 Stratford Tf Ti Multifuel Boiler Stoves BOILER TAPPING POSITIONS Stratford Tf70 Boiler Tappings Positions Stratford Tf90 Boiler Tappings Positions All dimensions in mm...

Page 27: ...Stratford Tf Ti Multifuel Boiler Stoves 27 BOILER TAPPING POSITIONS Stratford Ti 40 Inset Boiler Tapping Positions All dimensions in mm...

Page 28: ...ies while the fire is alight and care must be taken to ensure that effective circulation can occur around the primary circuit to carry heat away and thus stop boiling The output of any radiator instal...

Page 29: ...vent and ensure no air locks Check the circulation round the primary system and the heat leak radiator particularly when the pump is running to ensure circulation is not reversed Be sure that the chim...

Page 30: ...t gas appliances only c If clay or concrete flue liners used confirm that they are correctly jointed with socket end uppermost and state jointing materials used d If an existing chimney has been refur...

Page 31: ...AFS010 AFS010 AFS012 AFS012 AFS008 AFS008 AFS008 AFS008 AFS050 AFS051 AFS052A AFS116 AFS009 AFS009 AFS011 AFS011 2 Throat Plate 3 Grate Bar Set 4 Hot Plate 5 Operating Tool 6 Ashpan 7 Flue Spigot Par...

Page 32: ...ss Replacement Kit Complete with Gasket 10 Glass Clips Gasket 11 Hinge kit Comprises 2 Hinges 4 Fixings Per Set 12 Fire Door Rope Kit Complete with Door Rope Glue 13 Main Door Assembly Complete with H...

Page 33: ...mostat Assembly Includes Damper Fixing Control Knob 17 Thermostat Control Knob 18 Thermostat Damper Plate 19 Fire Bed Surround 20 Comb replacement with extension shaft 22 Replacement slot in grate bar...

Page 34: ...e of replacement shall be shared by the manufacturer and purchaser as follows During the first year of purchase the manufacturer will pay 100 of the cost of parts only During the second year the manuf...

Page 35: ...ase contact your Aarrow retailer Please keep all repair receipts safely Please ensure you have this manual available when an engineer visits as they will complete the service record chart Stratford Tf...

Page 36: ...G INSTRUCTIONS Model Serial No I ve checked it and it s O K Assembled by Checked by Date of Purchase Name and Address of Supplier Please ensure installer completes BOILER CHECK LIST on page 29 and INS...

Reviews: