Example: How many air filtration devices (each with 600 CFM rated airflow) would be required to 

provide 8 ACH (including a safety factor) in a 40ft L x 24ft W x 10ft H containment area? 

a.

 

V = 40ft x 24ft x 10ft = 9600ft³ 

b.

 

 Design ACH = 8 

c.

 

Quantity of AFD required = (9600ft³ x 8 ACH) / (600CFM x 60) = 76,800/36,000 = 2.13 

units 

d.

 

2.13 

units → 3 units required.

 

 

 

ELECTRICAL REQUIREMENTS 

1.

 

The PREDATOR® Portable Air Scrubber requires a minimum of 110 volts AC, 60 Hz to operate properly; 

however, maximum airflow performance requires 120 volts AC, 60 Hz. 

2.

 

Due to momentary start-up current surge, the unit requires a 15 amp circuit that is free of other loads. 

3.

 

Extension cords used for this unit must be UL-listed, heavy duty No. 14/3 AWG SJTW industrial grade 3-

wire type. Use of larger numerical gauge (lower capacity wire) power cord(s) may result in electrical 

shock, fire hazards and/or damage to unit. The cord(s) must be in good condition and in continuous 

lengths (no splicing) and should not exceed a total of 50 feet in length. Make certain that any extension 

cords used do not reduce power to the unit to less than 110 volts. Use of a voltmeter to confirm 

adequate voltage is recommended. 

4.

 

Check to ensure that any circuit to which the unit is connected is protected by a 15 ampere circuit 

breaker. The unit itself is equipped with a 12 amp circuit breaker. 

5.

 

This unit should be connected to a three-prong, properly grounded electrical outlet equipped with a 

Ground Fault Circuit Interrupt (GFCI) device.  A GFCI is an electrical safety device that will trip the circuit 

and stop the flow of electricity if leakage of current is detected. 

Important Note: The GFCI on this unit's control panel only detects leakage of current from the unit or 

an electrical device plugged into the GFCI.  This unit should be plugged into a GFCI receptacle at the 

power source to protect the power cord and the unit.  This GFCI will trip the circuit if it detects 

leakage of current from the power cord or unit. 

6.

 

To avoid personal injury, fire hazards and/or damage to the unit's electrical system and power cord, do 

not connect or disconnect the power cord to an electrical outlet unless the speed control switch is 

“OFF”. 

 

 

SAFETY INSTRUCTIONS 

 

REQUIREMENTS FOR SAFE OPERATION 

1.

 

Never allow unauthorized individuals or children to operate the unit at any time. 

2.

 

Abatement Technologies urges anyone operating PREDATOR® air scrubber units to wear the proper 

personal protective equipment and follow safe work practices in accordance with federal, state, local, 

provincial and employer regulations. 

3.

 

Check the condition of power cord(s) before using them. Damaged cords can cause fatal electric shock 

and/or motorized impeller failure. 

4.

 

Power cord(s) should never be exposed to water, heat, and/or sharp or abrasive objects.  In addition, 

they should never be kinked or crushed.  Avoid tightly wrapping the cords to prevent kinking of the 

internal wires. Always replace damaged power cords immediately. 

5.

 

Never pull the unit by the power cord. 

6.

 

Avoid running over power cords with utility equipment and vehicles. 

 

Summary of Contents for PREDATOR PRED750

Page 1: ...els PRED750 PRED750EC INSTRUCTION MANUAL U S PATENT D742495 CANADIAN PATENT 2852880 Ⓓ ABATEMENT TECHNOLOGIES INC Abatement Technologies Inc Abatement Technologies Inc Georgia USA 800 634 9091 Abatement Technologies Ltd Ontario Canada 905 871 4720 www abatement com ...

Page 2: ... N H502 Alternate Second Stage Filter 2 High Capacity Vapor Lock Carbon Filter P N VL1002 3 Final Stage 99 97 HEPA Filter P N H161606 99 4 HEPA Filter Retaining Brackets 5 Motorized Impeller located inside cabinet 6 Pre filter Access Door 7 Control Panel 8 Carrying Handle 9 Air Intake 10 nominal diameter 10 Exhaust Outlet 10 nominal diameter ...

Page 3: ...ernate carbon pre filter for capturing low concentrations of odors vapors gases and volatile organic compounds collectively known as OVG is also available Types of contaminants captured by particulate pre filters HEPAfilter or carbon filters Dirt Lung damaging particles Low concentrations of OVG Dust Metal fumes Low concentrations of Volatile Organic Compounds VOC Drywall dust Smoke Saw dust Mold ...

Page 4: ...ectiveness by exposing OVG particles to multiple passes through the Vapor Lock filter It is almost impossible to provide accurate estimates to two commonly asked questions how much time will it take to capture all of the OVG and how do I know when a carbon filter should be replaced Unfortunately unknown factors such as concentration levels fresh air intake volume temperature and humidity prevent e...

Page 5: ...ipped with a Ground Fault Circuit Interrupt GFCI device A GFCI is an electrical safety device that will trip the circuit and stop the flow of electricity if leakage of current is detected Important Note The GFCI on this unit s control panel only detects leakage of current from the unit or an electrical device plugged into the GFCI This unit should be plugged into a GFCI receptacle at the power sou...

Page 6: ... risk of fire or electrical shock do not use this unit with any solid state speed control device Do not use in a cooking area Warning Do not position the unit so that it is difficult to operate the disconnecting device The disconnecting device is the power cord plug Caution This unit is designed for indoor use only Warning This unit is equipped with an automatic restart motorized impeller that wil...

Page 7: ... 6 GFCI Receptacle Electrical safety device that will trip and stop the flow of electricity if leakage of current is detected from the unit or an electrical device plugged into the GFCI receptacle The PRED750 PRED750EC can supply a total of 8 amps of electrical power for additional equipment that is connected to the GFCI receptacle Do not exceed this 8 amp limit Note If the equipment connected to ...

Page 8: ...e pressure compared to adjacent spaces so any air leakage will be an outflow of clean air and not inflow of contaminated air This pressure differential can be established by a placing the unit inside the containment area and using it to pull air into the area by attaching flex duct between the inlet collar and a location outside of the containment area b placing the unit outside of containment are...

Page 9: ... filters can be changed while in the stacked configuration It is not recommended to stack more than 3 units high due to safety as well as the compounding weight of the units STORAGE AND TRANSPORT OF THE UNIT TRANSPORTING THE UNIT The PREDATOR Portable Air Scrubber should be transported in its normal position resting on its rubber feet If extremely poor road conditions exist or excessive shock and ...

Page 10: ... this manual Filters can be changed earlier if desired to maintain a minimum required flow rate The unit should be cleaned with a damp cloth or a water based cleaner sanitizer as needed Do not use harsh chemicals solvents or detergents to clean the unit Warning Keep electrical components dry as their exposure to liquids poses a safety hazard and can damage components Test the GFCI located on the u...

Page 11: ... not reusable therefore do not attempt to clean and reuse them Caution Abatement Technologies PREDATOR Portable Air Scrubber units are designed to meet or exceed standards for high efficiency air filtration equipment Use only Abatement Technologies parts including replacement filters Use of non Abatement Technologies parts and filters voids the product warranty and all performance claims Warning T...

Page 12: ...he HEPA filter is held into place by two metal brackets Remove the two screws from each bracket and then remove the HEPA filter from the machine 5 Insert the new HEPA filter with the pleats oriented vertically and the air flow directional arrow on the filter pointing towards the control panel the gasketed side of the HEPA filter will be against the internal wall Note The HEPA filter is delicate an...

Page 13: ...0 hours of protection against UV deterioration Transportability Heavy duty flip up style transport handle Stackability Units are stackable and can stack up to 3 units high Pre filter access Hinged no tools pre filter access door with turn and latch closure and neoprene gasket First stage pre filter 1 deep coarse particulate pre filter Part Number F621 Second stage pre filter 2 deep pleated particu...

Page 14: ...gth of flex duct or eliminate restrictions Remove carbon filter from polybag Note If the unit does not start or malfunctions after carefully following the TROUBLESHOOTING GUIDE call Abatement Technologies service department at 800 634 9091 U S or 905 871 4720 Canada for assistance COMPONENT REPLACEMENT Warning To reduce the risk of fire electrical shock or personal injury always turn the unit OFF ...

Page 15: ...fications shall be held for Purchaser s shipping instructions which instructionsPurchasershall furnishpromptlyuponrequest ATI sliabilityshallinnoeventextend beyond replacement repair or refund of the purchase price and ATI shall not be liable under any circumstances for special contingent or consequential damages nor for loss damages or expenses directly or indirectly arising from the use of the g...

Page 16: ...15 ...

Page 17: ...16 ...

Page 18: ...17 ...

Page 19: ...TCH13 CAM LATCH 2 13 HARDWRE153 HINGE 2 14 HARDWRE137 SHORT RUBBER FOOT 2 15 HARDWRE138 LONG RUBBER FOOT 2 16 1753 CONTROL PANEL BOX 1 17 ELE164 CAPACITOR 1 18 CTRLPNL101 CONTROL PANEL ASSEMBLY 1 19 1754 CONTROL PANEL PLATE 1 20 H5015 SPEED CONTROLLER 1 21 H5016 SPEED CONTROL KNOB 1 22 LAMP08 AMBER LAMP 1 23 LAMP10 GREEN LAMP 1 24 ELE71 GFCI RECEPTACLE 1 25 ELE152 12 AMP CIRCUIT BREAKER 1 26 ELE22...

Page 20: ...19 ...

Page 21: ...20 ...

Reviews: