5.3.2.1 Replacing the motor connector
Removing the motor connector
Preparations
Note/Illustration
Action
DANGER
Before doing any work inside the cabinet,
disconnect the mains power. For more
information, see
1
.
Open the door.
2
Location of wrist strap button:
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section
3
xx1900001446
Removing the motor connector
Note/Illustration
Action
Disconnect the following connectors for
the motor connector:
•
T4.X7, T4.X8, T4.X9
•
X1 - K2.X7 & X22
•
PE.5 & PE.6
1
Continues on next page
300
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
5 Repair
5.3.2.1 Replacing the motor connector