Power supply
Value
Mains
220/230 VAC, 1 phase
Voltage for OmniCore C90XT
+10%, -15%
Voltage tolerance
50/60 Hz
Frequency
±3%
Frequency tolerance
Note
The use of three phase power with delta connection (as sometimes used in North
Americas and some Asian countries) voids warranty. If the facility has a substation
with any type of delta connection, a grounded Y-configured transformer must be
installed before the robot controller.
Line fusing
There is no integrated fuse inside the OmniCore C90XT controller. Add an external
fuse (time-delay) or circuit breaker (class K) according to full load current, as
marked on the controller nameplate. The following table shows the recommended
rating for an external fuse or circuit breaker.
Description
Current (A)
Robot
10 A
220/230 VAC, 1 phase
IRB 1100
10 A
220/230 VAC, 1 phase
IRB 1300
10 A
220/230 VAC, 1 phase
IRB 910INV
Residual current
The OmniCore C90XT controller is designed to meet the following requirement of
residual current. When connecting the robot controller to the power supply, an
external earth fault protection (residual current device, RCD) is required based on
the following data.
Residual Current in controller (mA)
Robot
< 30 mA
IRB 1100
< 30 mA
IRB 1300
< 30 mA
IRB 910INV
Note
The integrator needs to make the dimensioning of the electrical installation to
meet the local electrical requirements.
Continues on next page
Product manual - OmniCore C90XT
41
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
2 Controller description
2.2 Technical data for OmniCore C90XT controller
Continued
Summary of Contents for OmniCore C90XT
Page 1: ...ROBOTICS Product manual OmniCore C90XT ...
Page 36: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 360: ...This page is intentionally left blank ...
Page 420: ...This page is intentionally left blank ...
Page 428: ...This page is intentionally left blank ...
Page 452: ...This page is intentionally left blank ...
Page 456: ......
Page 457: ......