xx1900001455
Description
Live (L)
1
Neutral (N)
2
Not used
3
Not used
4
Not used
5
Protective Earth, grounding
PE
Required equipment
Note
Equipment
L, N, PE
Main connection cable (single phase)
Details see
.
30 mA
External earth fault protection (residual current device,
RCD)
See
Standard toolkit for controller
Standard toolkit
Circuit diagram - OmniCore
C90XT
,
3HAC065464-009
Circuit diagram
Line fusing
There is no integrated fuse in side OmniCore C90XT controller. An external fuse
or circuit breaker must be added by the integrator, according to the full load current
rating. See
Connecting the power
The following procedure describes how to connect the main power to the controller.
CAUTION
Always inspect the connector for dirt or damage before connecting it to the
controller. Clean or replace any damaged parts.
Continues on next page
76
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
3 Installation and commissioning
3.5.5 Connecting power supply to and grounding the controller
Continued