Configuration
IM/265D/V-EN-02 265Dx,
265VS
45
Pos: 19.1 /Überschriften/1/J - L/Konfiguration @ 0\mod_1140688219031_3101.doc @ 3154
K
8 Configuration
Pos: 19.2 /Konfiguration, Parametrierung/Druck/Druckmessumformer/Allgemein/Sicherheitshinweis für die Konfiguration @ 1\mod_1147764542781_3101.doc @ 12488
Warning - General risks
There is no protection against accidental contact when the housing cover is open.
Do not touch conductive parts.
Pos: 19.3 /Überschriften/1.1/1-spaltig/V - Z/Werkseinstellungen @ 1\mod_1147859886843_3101.doc @ 12602
8.1
Factory settings
Pos: 19.4 /Konfiguration, Parametrierung/Druck/Druckmessumformer/Allgemein/Werkseinstellungen @ 2\mod_1150098636718_3101.doc @ 29461
Transmitters are calibrated at the factory to the customer's specified measuring range. The
calibrated range and tag number are provided on the name plate. If this data has not been
specified, the transmitter will be delivered with the following configuration:
8.1.1 Pressure transmitter with HART communication and 4 … 20 mA output current
Parameters
Factory settings
4 mA
Zero position
20 mA
Upper range limit (URL)
Output Linear
Damping 0.125
sec.
Transmitter failure mode
21 mA
Optional LCD display
0 … 100 %, linear
Any or all of the configurable parameters listed above - including the lower and upper range
values - can easily be changed using a portable HART handheld terminal or the PC operation
software SMART VISION with DTM for 2600T. Data regarding flange type and material, O-ring
materials, and type of filling liquid is stored in the device.