background image

 
The anti  
 
 
 
 

 
Figure 2 shows a possible position of the detectors in order to protect 
a long and narrow access (e.g. a glass window). 
WARNING:  do not use  this  position  if the sensors are exposed to 
direct sunlight. 
 
ANTI-RIP TAMPER  
The anti-rip tamper is realized through a magnetic contact made up 
by the reed that is on the back of the card  of the detector and by a 
magnet that shall be built in beneath  the  detector. Figure 3  shows 
how magnet and detector shall be installed.  
The  provided  template enables to properly position  the magnet with 
respect to the detector. 
Check that the magnet does not move from its position if the sensor 
is ripped. 
 
Tip:  before drilling and installing the anti-rip tamper, complete the 
installation and check that the position chosen for the detector 
actually covers the area to be protected.  If this is the case and  it is 
not necessary to find another position, remove the detector, install 
the magnet and mount the detector again. 
 

 

 

Figure 3 

 
To fix the detector: 
1) 

Remove the cover of the device by loosening the screws on the 
cover and lift it (figure 4). 

2) 

Fix the base  of the detector on the frame or where it is 
required, with two screws or screw anchors, as appropriate. 

 

 

 

Figure 4 

 
If you want to use also the external contact, it is necessary to drill the 
external part of  detector  frame. Figure 5 shows  in grey the  frame 
areas where it is necessary to make the hole to let the cable pass. 

 

 

 

Figure 5 

 

WARNNG!  Drilling the detector frame reduce the IP level of the 
device. The diameter of the hole should be as small as possible 
according to the size of the cable that shall pass. 
Be careful that water does not enter from the hole as it could damage 
the electronic circuits of the device. 
 
 
 
 
 
 
 
 
 
 
 

Both  external  contact  and tamper wires  can be connected  to the 
connection terminals (figure 6). 
IMPORTANT:  if the inputs were not disabled through the 
programming executed on the control unit, the non-used input 
(Tamper or Contact) has to be short-circuited through a jumper  on 
the terminal. 

 

 

 

Figure 6 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

2.2 

Programming 

To program the device: 
1.  Put the control unit into sensor programming mode. 
2.  Power the detector by removing the insulating strip of the battery. 
3.  Trigger  a transmission from the detector by passing a hand in 

front of the sensors. 

4.  Program the detector from the control unit. 
 
There are some parameters common to all detector types that are 
shown in the installation manual of the control unit and a group of 
parameters that are specific to the dual perimeter detector. 
The detector specific parameters are: 
 

Parameter  Value  Function 

SI 

(YES) 

Active anti-masking  

NO 

Inactive anti-masking  

OR 

IR sensors operation in OR mode 

AND  IR sensors operation in AND mode 

IR sensitivity: 2 pulse count 

IR sensitivity: 1 pulse count 

NO 

Disabled external contact 

SI 

(YES) 

Enabled external contact 

SI 

(YES) 

Active IR signal LED  

NO 

Inactive IR signal LED  

SI 

(YES) 

Active anti-rip tamper  

NO 

Inactive anti-rip tamper  

Underlined values are factory settings. 
 
The anti-masking function detects fixed obstacles at a distance of at 
least  25 cm from the IR sensors. Within 5 seconds from the 
detection, a tampering alarm is sent. 
If both a jamming and a tampering (tamper) attempts are detected, 
the first event occurred is signaled. 
 
IR sensors can be operated in OR or AND mode. 
In case of OR mode, it is enough that the sensor detects a movement 
to activate the alarm signal. In this way a  higher  sensitivity  is 
provided. 
In  case of AND  mode, both sensors shall detect the movement  in 
order to activate the alarm signal. The immunity to false alarms will 
increase. 
 
The pulse count adjusts the readiness to send the alarm. 
 
Signal  LED  (figure  5) is used to check the IR coverage. It turns on 
each time the IR sensors execute a detection. 
The LED can be visible also when the detector is closed. 
WARNING:  once you have executed the check and calibration, 
deactivate the LED signal in order to not reduce the battery 
autonomy. 
 
In case of enabled external contact, the detector transmits both the 
closing and the opening of the wired  contact  connected to the 
terminals. 
 
In case of deactivated anti-rip  tamper, the reed is inhibited and the 
device behaves as if the contact were always closed. 
In case of active anti-rip  tamper, the detector signals any  possible 
removal. 
 
The function Invia supervisione (Send Supervision) is active because 

it is a factory setting. 
 
 
 
 
 
 

2.3 

Completion and test 

Lay the cover back on the device and fix it with the screws. 
WARNING:  the coverage has to be laid  on the right side.  The 
coverage  openings  for IR sensors shall be above the battery 
compartment. 
 
Proceed with the  detector test, by following the testing instructions 
encompassed in the installation manual of the control unit. 
The LED turns on each time the sensors detect a movement within 
the covered area. This enables to check possible shaded areas and 
to move the detector, if required. 
At the end of the test, disable the LED signals through the 
programming.  
 
 

3  Maintenance 

3.1 

Cleaning 

To clean the device use a dry cloth. 
Regularly check that the IR sensor slot is clean and without any 
obstacle. 
 
 

3.2 

Battery replacement 

The battery in the detector shall not be disposed as urban waste 
(Directive, 2006/66/EC), as it is subject to separate waste collection in 
order to avoid environmental damages. 
Battery shall be replaced by qualified personnel. 
 
 
To replace the battery: 
1.  Put the control unit  into maintenance  status  (please refer to the 

installation manual of the control unit). 

2.  Remove the detector cover. 
3.  Remove the exhausted battery. 
4.  Insert the new battery. 
5.  Lay the cover back on the detector. 
6.  Execute the test of the detector to be sure it works. 
7.  Exit the maintenance status, if required. 
 
 

3.3 

Reset 

In order to execute the reset of the detector, remove and insert the 
battery again. 
A sensor already acquired on the control unit can be acquired again 
on the same control unit without executing the reset. 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

- 4 - 

- 5 - 

- 6 - 

- 7 - 

- 8 - 

- 9- 

Reviews: