364Ax-Gx Instruction Manual
27
Set the URV by Local Keys
Set the transmitter applied pressure as for Upper
Range Value. When th e applied p ressure is
stable push the Span lo cal adjustment key (S)
located on the terminal block and release. After
this operation the reading shall move to 20 mA. If
no changes occur repeat the operation.
Set the URV by Digital LCD Integral Display
To set the URV reading of the Digital LCD Integral Display (the engineering units have to be selected):
Navigate the Digital LCD Integral Display menu, select
Display
>
Display settings
>
Display URV (100%)
,
and the Span values may be available.
Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set the Display URV : 3 – 7 – 3 - Edit
To set the Transmitter URV without reference pressure:
Navigate the Digital LCD Integral Display menu, select
Device Config
>
Rerange
>
Rerange no pressure
>
Set URV
, and the URV values may be available
Select the desired value and confirm.
)
Digital LCD Integral Display Keys sequence to set the URV wihout pressure: 2 – 1 – 2 – 3 – Edit
To set the Transmitter URV with reference pressure:
Set the transmitter applie d pressure as for Upper Range value (100%). Navigate the Digital LCD Integral
Display menu, select
Device Config
>
Rerange
>
Rerange with pressure
>
Set URV (100%)
.
Select
OK
to start the autoadjust.
)
Digital LCD Integral Display Keys sequence to set the URV wih pressure: 2 – 1 – 1 – 2 – OK
Set the URV by CoMeter
URV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.
Set the URV by HHT
URV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.
Set the URV by PC
URV configuration by PC is available using dedicated Software. ABB c an provide t he references and the
Software. Please refer to the Software instructions for the appropriated operations.
Special functions
The transmitter has some functions to support the user in case of applications that require advance output
configuration.
Transfer functions
The 2600T Pressure Transmitter Series provides a selection of output functions, as follows: