364Ax-Gx Instruction Manual
23
Configuration
Default configuration
The data default configuration at the product delivery is the following:
Damping:
1 second
Units:
kPa
LRV:
0 kPa
URV:
equal to URL
Transfer function:
linear
Hardware setting:
Write protect mode in OFF, Failsafe direction High
Low saturation current: 3.8 mA
High saturation current: 20.5 mA
Low fail current:
3.7 mA
High fail current:
22 mA
LCD Display:
Set to display the PV value.
Easy Setup
To facilitate commissioning the 364 Display has the capability to run a sequence of predefined setup steps
with the main configuration settings.
When you start the Easy Setup you must continue up to the end to exit.
To start the Easy Setup:
Navigate the Digital LCD Integral Display menu, select
Easy Setup
.
)
Digital LCD Integral Display Keys sequence to start the Easy Setup: 1
Define the language
If the desired language is different from the default o ne select
Edit
then choose the desired language (see
the following table) scrolling with the up and down keys and confirming with
OK
. Select
Next
to continue.
English
Spanish
Italian
German
French
Define the Engineering Unit
If the desired Engineering Unit is different from the i ndicated, select
Edit
then choose the desired unit (see
the following table) scrolling up and down keys and confirm with
OK
. Select
Next
to continue.
mbar
millibar
mmH2O°C
millimeter of water at 4 degrees Celsius
g/cm
2
grams per square centimeter
inH2O°F
inches of water at 68 degrees Fahrenheit (20°C)
Kg/cm
2
kilo grams per square centimeter
inHg°C
inches of mercury at 0 degrees Celsius
Pa
pascal
ftH2O°F
feet of water at 68 degrees Fahrenheit (20°C)
kPa
kilopascal
mmH2O°F
millimeter of water at 68 degrees Fahrenheit (20°C)
torr
torr
mmHg°C
millimeter of mercury at 0 degrees Celsius
atm
atmosphere
psi
Pounds per square inch
MPa
Megapascal
bar
Bars
inH2O°C
inches of water at 4 degrees Celsius
Define the Lower Range value (LRV)
If the desired LRV is different from the default one select
Edit
, then choose the desired value for the digit in
reverse color with the up and down keys and confirm with
Next.
Repeat the operation for the seven digits
and confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum allowed values are indicated on the display.
Define the Upper Range Value (URV)
If the desired URV is different from the indicated select
Edit
, scroll the desired value for the digit in reverse
color with th e up and down keys an d confirm with
Next.
Repeat the operation for the seven digits a nd
confirm with
OK.
Select
Next
to continue.
Note: the minimum and the maximum allowed values are indicated on the display.
Run the Zero Scaling
In case a Zero Scaling is required apply the pressure for the Zero and select
OK
. Wait for the auto-set end
(the bargraph will indicate the working progress). Select
Next
to continue.
Define the Damping
If the desired Damping is different from the indicated value change it with the up and down keys and confirm
with
OK.