background image

Instruction 

Leaflet

I.L. 

ABB Power T&D Company Inc.

Relay Division

Coral Springs, FL 33065

RCL

Effective: February 1966

Supersedes 

I.L

 41-661.2 

Dated May 1984

Automatic ReclosingRelay

Q

 Denotes Change From Superseded 

issue

in 

FT-21 Case

CAUTION

Before putting relays into service, remove all

blocking which may have been inserted for the

purpose of securing the parts during shipment,

make sure that all moving parts operate freely,
inspect the contacts to see that they are clean and
close properly, and operate the relay to check
the settings and electrical connections.

APPLICATION

The type RCL automatic reclosing relay is used

for automatic reclosure of a-c or d-c electrically
operated circuit breakers after they have been
opened by overcurrent or other protective relay
action. The relay may be adjusted to provide

several reclosures at predetermined time inter-

vals, so that in case the breaker does not remain

closed after the first reclosure additional reclo-
sures will be made. The first reclosure usually
is an instantaneous reclosure through preclosed
contacts since system operating experience has
shown that the majority of faults are of a tem-
porary nature, such as lightning flashovers, and

will not be re-established after interruption of the

fault current. Consequently, service interruption

can be minimized by the use of an instantaneous
reclosure. However, the first reclosure may be
delayed if desired.

In case the circuit breaker does not remain

closed after the first reclosure, the relay will make
additional reclosures at suitably graded intervals.
It is common practice to make two additional
reclosures, but the relay may be adjusted to make
any number up to a total of six reclosures if de-
sired. If the breaker does not remain closed after
the final reclosure, the timing drum stops in the

“Lockout” position, and any further attempts at
reclosure must be made by manual operation of
the control switch. However, if the breaker re-

mains closed after any automatic reclosure, or,
subsequently, after manual reclosure, the relay

timing drum will advance to and stop at the
“Start” position, where the relay is in readiness
for another cycle of automatic reclosures follow-

ing the next tripping of the breaker.

For any automatic reclosing application, the

de-rating factors for breaker interrupting ability
should be checked when choos&g  any particular
reclosing cycle. Also, when using instantaneous
first reclosure it is necessary that the protective
relays open their contacts within 10 cycles or
less after the breaker is tripped in order that the
trip circuit will be de-energized before reclosure
takes place.

CONSTRUCTION

As shown in Fig. 2, the RCL relay consists of a

Olatching solenoid unit, Y, a synchronous motor

driven timing unit, and a telephone relay unit, X.

TIMING UNIT

The timing unit contains a synchronous motor

and gear train mounted behind the front subbase.

The gear train drives a drum with cams, which

actuate contacts 1, 2 3, 4 and 14. Cam #5
actuates the Y unit latch to reset the Y unit and
close the Y 13 contact. Cams # 1 and #2, which
operate contacts 1 and 2 respectively, are notched
and are not intended to be adjusted in the field.

Cam #3 is a series of flat springs secured by

screws, which can be located at any point on the

All possible contingencies which 

may 

arise during installation, operation or maintenance, and all details

and variations of this equipment do not purport to be covered by these instructions. If further information
is desired 

by 

purchaser regarding #is particular installation, operation or maintenance of this equipment,

the local  ABB Power T&D Company Inc. representative should be contacted.

Printed in 

USA

Courtesy of NationalSwitchgear.com

Summary of Contents for 41-661.2A

Page 1: ...d after the final reclosure the timing drum stops in the Lockout position and any further attempts at reclosure must be made by manual operation of the control switch However if the breaker re mains closed after any automatic reclosure or subsequently after manual reclosure the relay timing drum will advance to and stop at the Start position where the relay is in readiness for another cycle of aut...

Page 2: ...r of the relay against a spring A micarta disc on the front end of the plunger actuates contacts Y5 and Y7 As the disc moves to the rear it releases the latch arm When released the latch arm is rotated counterclockwise by the tension of the moving contact spring of contact Y13 and a small helical spring This rota tion blocks the full reset when Y is de energized o Thus the Y unit has three positio...

Page 3: ...I L 41 66L2A i I j Fig 1 Type RCL Reiay 3 Courtesy of NationalSwitchgear com ...

Page 4: ...I L 41 661 2A Fig 2 Internal Schematic of the RCL Relay in Type FT21 Case 4 Courtesy of NationalSwitchgear com ...

Page 5: ...I L 41 661 2A OFig 3 Cam and Y Unit Contact Positions 5 Courtesy of NationalSwitchgear com ...

Page 6: ...t The relay is now ready for another reclosure as soon as contact 3 is closed by the 3 cam spring The drum will continue to rotate since the motor is energized through S2b and l contacts Second and Third Reelosures At 15 and 45 seconds the 3 contact closes to reclose the breaker After each reclose the Y unit is unlatched by the action of cam S 6 Lockout When the drum reaches the lockout position t...

Page 7: ...with the relay for thick panel mounting The terminal stud may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench DRUM SPEED To change the drum speed loosen the clamp ing screw at the edge of the drum speed dial depress the push rod on the drum and rotate the motor and gear assembly to the desired speed position by pushing on one or more of t...

Page 8: ...brasive material for cleaning contacts is not recommended because of the danger of embed ding small particles in the face of the soft silver and thus impairing the contact MOTOR LUBRICATION The motor bearing contains a supply of special lubricant sufficient for from three to five years service This lubricant does not congeal at low temperatures and permits satisfactory operation of the motor at am...

Page 9: ...in o I O lO l i O UJ m UJ X J o a o o 0 10 o T l u 3 _Q in 4 _o OT T 3 _D i o X in Sxo t s X z K i z 3 Z o in o n J 1492B04 mmediate and Two Time Delay Reclosures r Coil Energized nent Fault Instantaneous Trip Lockout After First Reclosure 9 ...

Page 10: ... X U N I T 101 CONTROL SWITCH 79 RCL RELAY SOLENOID 201 AUXILIARY RELAY FOR Y U N I T SUPERVISORY TRIP LOCKOUT RELAY 201X AUXILIARY RELAY PR PROTECTIVE RELAY r L 41 661 2A 3U r CM w ft fO o Qy P2 Hr oo x CM o m CM n u CM if s i 8 Nr CM CM X 1 LD LO CO Mi CO 10 oo K2 S n d PtVH 3c Mi PJrO 5 7 0 7 CD X X X X C CM in If 5 CO X 3 5 li ce CO E cr cc cc o o QC o LU 2 S 2 as xa o o o H I I I I 5 CM I D t...

Page 11: ...ES _ 5 375 136 53 4 K0I6 397 250 _ 6 35 0 kl 03l I 03I 1 031 1 031 H 26 19 26 19 26 19 26 19 1 I 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE rA 5 16 18 SCREW FOR THICK PANELS fie 09 USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 7 1 1 0 yl 25 4 f i l 3 5A 7 9 i 1 813 i 2 0 l 46 05 i 50 8 10V 2 4 6 8 I V v 516 13 11 H 03...

Page 12: ...ose application because sensitive auxiliary relays in the breaker close circuit may stay picked up All possible contingencies which may arise during installation operation or maintenance and a details and variations of this equipment do not purport to be covered by these instructions If further informa tion is desired by purchaser regarding this particular installation operation of maintenance of ...

Reviews: