26
Electromagnetic Flowmeter Converter
Submenu/Parameter
Entry Type
Comments
Operating mode “Piston Pump” for pulsating flows.
In this operating mode an improved reproducibility is achieved in
the flow signal measurements for pulsating flows in piston pump
applications.
In order to realize a quiet instantaneous flow indication and a
smooth current output a special software filter can be activated in
the converter. The filter should be turned “on” for piston pump
operation. The damping time should be selected greater than
2.4 s, otherwise the software filter will not be operational.
Selection of the flow direction
Forward/reverse or forward only
If the flow is in the reverse direction when forward only is
selected, the flow direction indicator
“R” in the display blinks
and the flowrate is set to 0 %.
Normal/Inverse
Reverse the forward/reverse flow direction indicators.
See display.
When a converter is exchanged the meter location
parameters can be uploaded into the replacement
converter.
After the start-up configuration has been completed or after
instrument settings have been changed, the new or revised
parameter settings can be stored in the external EEPROM.
Software version
In the 1st line the instrument designation is displayed together
with the revision date of the software 01/00. In the 2nd line the
software designation (D699B154U01, for HART D699B164U01)
and the software version are displayed.
numeric
An alphanumeric meter identification TAG-Number, with up to 16
characters, can be entered utilizing lower and upper case letters
and numbers.
numeric
Only for ABB Fischer & Porter Service.
Operating mode
Piston pump
Flow direction
Forward/reverse
←
Direction Ind.
normal
Load data from
ext. EEPROM
Store data in
ext. EEPROM
Model Number 01/00
Part number
TAG Number
Service Code