Electromagnetic Flowmeter Converter
5.2.
Parameter Overview Standard Software (HART-Protocol see Page 33) and Data Entry
Submenu/Parameter
Entry Type
Comments
from table/numeric
Data can only be entered when the program protection has been
turned off.
on / off
If a value other than “0” (factory default setting) has been selected
for the Prog. Prot. Code, then the program
protection can only be turned off after the correct
PP-Code (1–255) has been entered.
After the program protection has been turned off, parameters can
be changed.
numeric
After the program protection has been turned off, it is also
possible to change the PP-Code.
Enter the old PP-Code.
0 = Factory default setting
Enter the new PP-Code (0–255)
from table
German, English, French, Finnish, Spanish,
Italian, Dutch, Danish or Swedish can be
selected as the language for the display.
from table
Exit the submenu
Installed flowmeter primary size, see Instrument Tag.
1/25” - 96” [DN 1 – DN 2400].
Select with arrow keys. Displayed in mm and inches.
When the size changes, Q
max
is automatically set to 10 m/s.
The pulse factor is set 1.
The short Model Number for the flowmeter primary:
10DS2110/3110/DS21/DS41/DS41 > 14” [DN 300]/DH
10DI1425 <20” [DN 500]
10DI1425 >16” [DN 400]
10DS3111 E >12” [DN 300]
10D1462/1472
10D1422
Switch S901on the connection board must be set for the
specific Model Type.
Automatic setting based on the flowmeter primary size
selection
numeric
Flow range end value for forward and reverse flow directions
Min. flow range setting 0–0.5 m/s
Max.flow range setting 0–15 m/s.
Flow range end value can be set between 0.5 and 15 m/s.
=
to
* Prog. Protection*
on
ENTER
* Prog. Protection*
off
PP-Code
0
Prog. Protection
off
Prog. Protection
ENTER
Old PP-Code?
0
Prog. Protection
Language
English
Submenu
Primary
C/CE
ENTER
Meter size
250 mm
10 in
Primary
10DS2110/3110
RangeMax
10 m/s
1800.00
m3/h
Qmax
400.00
m3/h
0,05 Ran ge
ma x
⋅
1,5 R ange
m ax
⋅