Electromagnetic Flowmeter Converter
5.5.3 Parameter Overview HART-Protocol, Data Entry, see Pages 19 to 26
Submenu/Parameter
Submenu/Parameter
Entry Type
Comments
Operating modes: standard or piston
pump
The Short Model Number of the
flowmeter primary
For HART-Protocol always 4-20 mA
Current output during an alarm condition,
0 % = 4 mA or 130 % = 26 mA
HART-Protocol
For instrument addresses
≥
1, the meter
operates in the Multidrop-Mode (4 mA).
For address 0 the range is 4-20 mA
1200 Baud
Transmission speed
Prog. Protection
on
Density
1.0000 g/cm3
Language
English
Display in
l/min
Meter size
25 mm
1 in
System zero
0.0000 Hz
Units Qmax
l/min
Submenu
Operating mode
RangeMax
10 m/s
200.000 l/min
ENTER
Operating mode
Standard
Qmax
50.000 l/min
Primary
DS41....
Units totalizer
l
Submenu
Current output
Pulse factor
1.000 /l
ENTER
Current output
4-20 mA
Pulse width
30.000 ms
Iout at Alarm
0 %
Max. Alarm
90 %
Submenu
Data link
Min. Alarm
012 %
ENTER
Communication
HART
Low flow cutoff
1.0000 %
Instr. Address
000
Damping
5.0000 s
Baudrate
1200 Baud
Filter
off