background image

 

Page 10

 

© Copyright 2023 ABB. All rights reserved. 

 

827E MBS_MAN

 

Rev. 2.4

 

 

2.4 Electrical  Specifications 

(continued)

 

 

 

 Utility AC Power Input

 

Input 1:

 

120 VAC, 60 Hz, 240 Amp max.  AC, 1 Phase

 

 Inverter Output AC Power Input

 

Input 2:

 

120 VAC, 60 Hz, 240 Amp max.  AC, 1 Phase

 

 48VDC Input

 

Input 3:

 

48VDC, 1.3 Amp

 

 Maintenance Bypass Output

 

Out put 1:

 

120 VAC, 60 Hz, 240Amp max.  AC, 1 Phase

 

CAPACITY:

 

FIGURE 2

-

3:  MBS Wiring Diagram

 

2.5 827e Inverter System E/W MBS Wiring Diagram

 

Summary of Contents for 6310408P

Page 1: ...Page 1 Copyright 2023 ABB All rights reserved 827E MBS_MAN Rev 2 4 PRODUCT MANUAL Maintenance Bypass Panel For 827E Inverter Plant 6310408P 6310408P 1 ...

Page 2: ... 21 2 1 GENERAL 9 2 2 MAINTENANCE BYPASS PANEL DESCRIPTION 9 2 3 MECHANICAL DIMENSION 9 2 4 ELECTRICAL SPECIFICATION 9 2 5 827e INVERTER SYSTEM E W MBS WIRING DIAGRAM 10 3 SYSTEM INSTALLATION 35 3 1 GENERAL 11 3 2 UTILITY COMMERCIAL AC INPUT CONNECTIONS 12 3 3 INVERTER INPUT CONNECTIONS 13 3 4 AC LOAD OUTPUT CONNECTIONS 13 3 5 INPUT ALARM CONNECTIONS FROM THE 827E INVERTER PLANT 14 3 6 OUTPUT ALAR...

Page 3: ...t 1 972 244 WATT 9288 or toll free at 877 546 3243 to request a quote RETURN REPAIR Please contact 1 972 244 WATT 9288 or toll free at 877 546 3243 to request a Return Material Authorization RMA for defective equipment Product Information Please take a moment when the product is new to fill in this information This data will allow faster service when calling ABB Power to order accessories spare pa...

Page 4: ...on subjects the user to electrical shock that may cause serious injury or death Pas la tentative pour traiter cet équipement si c est ou a été exposé à une haute condition d humidité Il est recommandé l équipement s est retourné à ABB POWER deux être convenablement essayé Traiter cet équipement pendant une haute condition d humidité expose l utilisateur au choc électrique qui peut causer la blessu...

Page 5: ...of California to cause cancer and birth defects or other reproductive harm Wash hands after touching batteries Cet équipement peut connecter des piles mener acides Les postes de pile les terminaux et les accessoires apparentés contient l avance et les premiers composés les produits chimiques connus à l état de Californie pour causer les défauts de cancer et naissance ou l autre mal reproducteur La...

Page 6: ...r de courant alternatif ou DC n est pas appliqué au système 5 Fuse holders fuses and circuit breakers are not to be loaded to more than 80 percent of their ampere rating Fondez les supports fusibles et des disjoncteurs ne doivent pas être chargés à plus de 80 pour cent de leur estimation d ampère 6 This equipment is intended for restricted access locations only Cet équipement est projeté pour les ...

Page 7: ... AC LEDs indicate the presence of those source voltages they do not prevent the load transfer from occurring It is the operator s responsibility to know if the source that is being transferred to is an energized source An alternate purpose of the MBS is to collect alarms from the inverter shelves and to extend these alarms to the plant monitor The status of the consolidated alarms is indicated by ...

Page 8: ...Page 8 Copyright 2023 ABB All rights reserved 827E MBS_MAN Rev 2 4 ...

Page 9: ...08P 1 30KVA Bypass Panel 2 2 Maintenance Bypass Panel Description The maintenance bypass panel provides a means to move a load from the inverter plant to utility commercial AC source 2 3 Mechanical Dimensions HEIGHT 6 97 inches WIDTH 23 00 inches DEPTH 14 88 inches 2 4 Electrical Specifications Utility AC Power Input Input 1 120 VAC 60 Hz 60 Amp max AC 1 Phase Inverter Output AC Power Input Input ...

Page 10: ...wer Input Input 1 120 VAC 60 Hz 240 Amp max AC 1 Phase Inverter Output AC Power Input Input 2 120 VAC 60 Hz 240 Amp max AC 1 Phase 48VDC Input Input 3 48VDC 1 3 Amp Maintenance Bypass Output Out put 1 120 VAC 60 Hz 240Amp max AC 1 Phase CAPACITY FIGURE 2 3 MBS Wiring Diagram 2 5 827e Inverter System E W MBS Wiring Diagram ...

Page 11: ... and the first Inverter shelf as well as from Inverter shelf to inverter shelf to allow air flow between units for proper heat dissipation refer to Figure 3 1 CABLING A Remove the maintenance bypass panel from the shipping container B Install the panel as follows 1 Ensure there is proper clearance in the rack to install the maintenance bypass panel 2 Put the panel into position and secure with the...

Page 12: ... input connection is made via a compression screw Maximum size cable is 350 MCM C Ensure that commercial AC power is protected from the customer side of the bypass panel D If used with an 827E Inverter Plant a circuit breaker is provided in the inverter shelf to provide over current protection or disconnect means between the inverter and MBS E Over current protection for Commercial AC fed to the M...

Page 13: ...m to the inverter input connections on the maintenance bypass panel as shown in Figure 3 4 Each input connection is made via a compression screw Maximum size cable is 6 GA Figure 3 4 Inverter Input Connections 3 4 AC Load Output Connections WARNING Ensure that all input power is removed from the maintenance bypass panel before beginning to perform the load connections from the maintenance bypass p...

Page 14: ...ass Panel 3 5 Input Alarm Connections From The 827E Inverter Plant A The maintenance bypass panel provides input alarm connections for each of the four inverter shelves Inverter Shelf Number Panel Inverter Shelf 1 J4 Inverter Shelf 2 J3 Inverter Shelf 3 J2 Inverter Shelf 4 J1 827E Inverter Shelf Figure 3 6 Alarm Input Connections from 827E Inverter Shelves ...

Page 15: ... out connections Table 3 1 Alarm Pin Out Connections for J6 MAJOR 1 CLOSE ON ALARM Any Major Alarm from inverter shelves 1 2 3 or 4 Or Two or more Minor Alarms from any inverter shelf 3 COMMON 2 OPEN ON ALARM MINOR 4 OPEN ON ALARM Any Minor Alarm from inverter shelves 1 2 3 or 4 6 COMMON 5 CLOSE ON ALARM CAPACITY 7 OPEN ON ALARM A Capacity Alarm from any of the inverter shelves 1 2 3 or 4 9 COMMON...

Page 16: ...DC protected with a 1 Amp fuse from an external source J7 48VDC Battery Input Compression StyleTerminal Block Figure 3 8 BAT Input Connections Pin 1 GROUND 3090125P 2 Compression 14 20 AWG Pin 2 BATTERY 3 8 Verify Installation Is Complete utility position and verify that the commercial AC power takes over the loads Move the switch back to the ...

Page 17: ...s not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2023 ABB All rights reserved ...

Reviews: