IEC Symbol Name
Node Type
IEC Symbol
Definitions
ANSI Y32.2/
IEEE 315
Symbol
Definitions
Category
Select button, 11 = Undefined
30
Texts
Indication button, 00 = Middle
position
31
Texts
Indication button, 01 = Open
31
Texts
Indication button, 10 = Closed
31
Texts
Indication button, 11 =
Undefined
31
Texts
6.2.3
Bay configuration engineering
A page with a single line diagram and measurements contains active living objects.
The object values are updated by the IED periodically (measurement) or in case of
an event. Once the symbols are placed on the HMI page they must be linked to the
corresponding function block in the application configuration, which protects or
controls the object that the symbol on the HMI page represents.
Creating a complete HMI display page
Procedure:
1. Make a sketch how to present the single line diagram.
2. Place the apparatus, transformer and other symbols that are needed for the
single line diagram into the raster boxes.
3. Add connection points where needed.
4. Link the apparatus symbols with line elements.
5. Adjust the text symbols while writing to north, east, south or west. Use the
object property window to do it.
6. Place measurements when needed.
7. Edit the name, unit and number of decimals of the measurements.
8. Select each object that has a dynamic link and do the link to the corresponding
process object, see
.
9. Check to select the correct function block. Function blocks of the same type
can have different instance numbers.
10. Validate that all links are done.
11. Save the complete picture.
12. Repeat the steps for all pages when more than one is needed.
13. Write the display configuration to IED from the GDE tool.
1MRK 511 261-UEN -
Section 6
Local HMI engineering
650 series
81
Engineering Manual