background image

- 4 -

OPERATIVE LIMITS

The transmitter operates on a minimum voltage of 10.5 Vdc to
a maximum of 55

 

Vdc and is protected against polarity

inversion.

Note - The transmitter operates from 10.5 to 42

Vdc with no load (a load up to 620 

 allows operation

up to 55 Vdc). For EEx ia and intrinsically safe (FM,
CSA and SAA) approval power supply must not
exceed 30 Vdc.In some countries the maximum
power supply voltage is limited to a lower value.

Installing optional devices the minimum voltage increases to:
- 10.5 Vdc with no option or with integral digital display
- 10.7 Vdc with output analog indicator
- 12.5 Vdc with output LCD indicator
- 12.1 Vdc with surge protection
- 14.1 Vdc with LCD indicator and surge protection
- 13.1 Vdc with LCD CoMeter

The total loop resistance is indicated in the figure and
expression below.

The total loop resistance is the sum of the resistance of all
elements of the loop, including wiring, conditioning resistor,
safety barriers and additional indicators (excluding the
equivalent resistance of the transmitter).

Where a configuration device (HART), such as the Hand Held
Communicator or a Modem is likely to be used, a resistance of
250 ohm minimum should be present between the power
supply and the point of insertion of  these devices, to allow
communication.

Several types of safety barriers, either passive or active, can be
satisfactorily used in conjunction with the Smart 600T EN
transmitter. Nevertheless, in case of use of active barriers,
check with the supplier if the model  is suitable for use with
smart transmitters allowing the connection of the configuration
devices in the "safe" or non-hazardous area.

    WARNING - The transmitter may be used as a

safety accessory (as defined by the Pressure Equipment
Directive 97/23/EC) i.e. as part of a shutdown system.
In this case it is recommended to select the correct fail safe
mode for the 4-20 mA signal (as per Namur NE43
recommendation).
See also the instructions relevant to fail safe selection (Up/
Down scale mode) in the addendum to the instruction
manual on "Use of hardware links on the secondary
electronics" .

R (k

) =

Supply voltage - min. operating voltage (Vdc)

22

Supply voltage

Total loop resistance 250

(ohms)

2020

25 (ref.)

10.5

55 (volts)

42

4 to 20 mA and

HART digital communication

620 

4 to 20 mA only 

600

Temperature limits 

°

C (

°

F) :

• Ambient (is the operating temperature)

All models and sensors can withstand without damages or
leakages temperatures from -40 to +85 

°

C, -40 to +185 

°

F.

-20 

°

C, -4 

°

F for Viton gaskets.

See the instrument data sheets for temperature effect on
response time and accuracy.

Note: For Hazardous Atmosphere application see the

temperature range specified on the certificate/approval
relevant to the aimed type of protection.

• Process (1)
Lower limit
- refer to lower ambient limits
- -20

°

C (-4

°

F) for Viton gaskets

Upper limit
- Silicone oil and KTFILL-1 filling : 120

°

C (248

°

F) (2)

- Inert fluid filling : 100

°

C (212

°

F) (3)

(1) Process temperature above 85

°

C (185 

°

F) requires derating the

ambient limits by 1.5 : 1 ratio.

(2) 100

°

C (212

°

F) for application below atmospheric pressure

(3) 65

°

C (150

°

F) for application below atmospheric pressure

Pressure Limits
For model number see the first five characters of Product
Code on label Ref. A.
The sensor code is the sixth character.

•  Lower : 0.067 kPa abs, 0,67 mbar abs, 0.01 psia
   (0.13 kPa abs, 1.33 mbar abs, 0.02 psia for sensor code A).
   Double the lower limit with inert filling

• Upper
   - model 6X1ED, EG, EA
   sensor codes B to W : 14 MPa, 140 bar, 2030 psi
   sensor code A : 8 MPa, 80 bar, 1160 psi
   sensor code U : 25 MPa, 250 bar, 3620 psi
   - model 6X1EE :
   all sensor codes : 25 MPa, 250 bar, 3620 psi
   - model 6X1EH :
   all sensor codes :1 MPa, 10 bar, 145 psi
   - model 622ED :
   sensor codes R, E, F : 42 MPa, 420 bar, 6090 psi
   sensor code L : 32 MPa, 320 bar, 4640 psi
   - model 6X1ES
   10 MPa, 100 bar, 1450 psi or the following flange/fitting

rating of the seal, whichever is less.
• flanged seals (S6E/S6F)
ANSI CL 150 : 2 MPa, 20 bar, 290 psi
ANSI CL 300 : 5 MPa, 50 bar, 725 psi
ANSI CL 600 : 10 MPa, 100 bar, 1450 psi
ANSI CL 900 : 16 MPa, 160 bar, 2320 psi
DIN ND 16 : 1.6 MPa, 16 bar, 230 psi
DIN ND 40 : 4 MPa, 40 bar, 580 psi
DIN ND 64 : 6.4 MPa, 64 bar, 930 psi
DIN ND 100 : 10 MPa, 100 bar, 1450 psi
DIN ND 160 : 16 MPa, 160 bar, 2320 psi
• sanitary seals (S6S)
2in Triclamp : 3.8 MPa, 38 bar, 550 psi
3in Triclamp : 2.4 MPa, 24 bar, 350 psi
4in Triclamp : 1.7 MPa, 17 bar, 250 psi
F50/F80 Union nut : 2.5 MPa, 25 bar, 360 psi

Summary of Contents for 6X1ED

Page 1: ...Instructions Warning An instruction that draws attention to the risk of injury or death Caution An instruction that draws attention to the risk of damage to the product process or surroundings Although Warning hazards are related to personal injury and Caution hazards are associated with equipment or property damage it must be understood that operation of damaged equipment could under certain oper...

Page 2: ...f the transducer diaphragms material fill fluid range limit and identification number Fig 1 Product identification Ref B Primary Unit Ref A Ref C Ref D Ref D Ref A DIN TYPE HOUSING BARREL TYPE HOUSING SERIAL NUMBER URL DIAPHRAGM MATERIAL FILL FLUID A Safety Marking plate ref C is fitted when the transmitter is requiredtocomplywithhazardousarearegulations e g flame proof or intrinsic safety protect...

Page 3: ...t The transmitter may be mounted on a vertical or horizontal 2 inch pipe figg 5 and 6 by means of the same mounting bracket Note for other installation details see the relevant Addendum Fig 5 Mounting on 2 vertical pipe Note High side may be marked H or Low side may be marked L or WARNING For installation in Hazardous Areas i e areas with dangerous concentrations of e g gases or dusts that may exp...

Page 4: ...e secondary electronics R kΩ Supply voltage min operating voltage Vdc 22 Supply voltage Total loop resistance 250 ohms 2020 25 ref 10 5 55 volts 42 4 to 20 mA and HART digital communication 620 4 to 20 mA only 600 Temperature limits C F Ambient is the operating temperature All models and sensors can withstand without damages or leakages temperatures from 40 to 85 C 40 to 185 F 20 C 4 F for Viton g...

Page 5: ...e 0 12 mm 0 005 in per year B Concentration and Temperature Limited NR Not Recommended No Data Available Numbers indicate the maximum allowable temperature C for a generally suitable material NOTE Data of the following table are based on information from manufacturers All data is based on a temperature of 20 C 70 F unless noted otherwise Since corrosion involves many more variables than this table...

Page 6: ... 6 CORROSION TABLE ...

Page 7: ... 7 CORROSION TABLE ...

Page 8: ... 8 CORROSION TABLE ...

Page 9: ... 9 CORROSION TABLE ...

Page 10: ... damaged if in replace WARNING Assembling flanges with incorrect fixing bolts and nuts and improper O rings can cause fracture or overstressing of bolts and release of pressurized process material Use only official spare parts and do not exceed the specified torque limits DO NOT REMOVE the O ring fitted in the sensor neck it provides the housing a degree of protection a Refit the flange fixing bol...

Page 11: ...screw Blind cover Flange bolts Analog or digital output indicator or CoMeter Extended windowed cover Blind cover Windowed cover Microprocessor driven integral display Tang screw Terminal blocks assembly Sensor assembly Calibration screws Nameplate DISMANTLING AND REASSEMBLY ...

Page 12: ... media D Dust dangerous media T50 C Maximum surface temperature of the transmitter enclosure with a Ta ambient temperature 40 C for Dust not Gas with a dust layer up to 50 mm depth T95 C As before for Dust for a Ta 85 C Note the number close to the CE marking of the transmitter safety label identifies the Notified Body which carries out the surveillance for the production of the transmitter The ot...

Page 13: ...eas continuous hazard with its process part only whereas the remaining part of the transmitter i e its enclosure can be used in Zone 1 Gas only see sketch below Reason of this is the process part of the transmitter normally called primary transducer that provides inside separation elements to seal off the electrical sensor from the continuously hazardous process according to the EN50284 and EN5001...

Page 14: ... 14 ...

Page 15: ...conformity with the following standards EN 50 081 1 1992 Electromagnetic compatibility Generic emission standard Residential commercial and light industry according to EN55022 1995 EN 50 082 2 1995 Electromagnetic compatibility Generic immunity standard Industrial environment according to EN61000 4 2 1998 EN61000 4 3 1998 EN61000 4 4 1995 EN61000 4 5 1995 ENV50141 1993 following the provisions of ...

Page 16: ... 16 PED600TEN Rev 1 ...

Reviews: