25
The following table displays the options that
can be changed by the user.
—
4 .5 User settings
—
Table 10: User settings
Submenu
Available settings
Default settings
Password
Key the password
USER
Language
[English][Deutsch][Español]
English
User password
[disabled] [Enabled]
[disabled]
Audible alarm
[enabled] [disabled]
[enabled]
Output voltage
[208V] [220V] [230V] [240V]
Can be changed in standby
mode and bypass mode
[230V]
Output frequency
[autosensing] [50HZ][60HZ]
[autosensing]
Power strategy
[normal] [high efficiency] [converter]
[normal]
Auto bypass
[enabled] [disabled]
[enabled]
Auto restart
[enabled] [disabled]
Authorize the product to
restart automatically when
mains recovers after a
complete battery discharge.
[enabled]
Dry in
[Disabled] [SON] [SOFF] [Maintain bypass]
[Disabled]
Dry out
[Load powered] [On battery mode]
[Battery low] [Battery disconnected]
[Bypass output] [UPS normal]
[Load powered]
Start on battery
[enabled] [disabled]
[enabled]
External battery modules
[0~20]
According to model
External battery AH setting
[0~300]
According to model
Battery remaining time
[enabled] [disabled]
[enabled]
Charger current
[0~4] 0~4A for standard model
[0~12] 0~12A for long backup model
[4A] for 6-10 kVA
Site wiring fault alarm
[disabled] [enabled]
[disabled]
LCD contrast
[-5 ~ +5]
[+0]