37
—
Appendix A
CS141 SNMP card available parameters (valid for
CS141 Basic, CS141 ModBus, CS141 Advanced) .
The parameters available for CS141 SNMP cards
are shown below.
Parameter
Units
Type
Available interface
Modbus register
Measurement Parameters
Input Voltage
V
Input
Webserver / Modbus
104
Input Frequency
Hz
Input
Webserver / Modbus
111
Output Voltage
V
Output
Webserver / Modbus
97
Output Load Percentage
%
Output
Webserver / Modbus
100
Battery Voltage
V
Battery
Webserver / Modbus
110
Battery Capacity
%
Battery
Webserver / Modbus
103
Temperature
°C
Environmental
Webserver / Modbus
107
UPS Status Information
On shutdown
Webserver / Modbus
109
On inverter
Webserver / Modbus
109
On battery
Webserver / Modbus
109
UPS Alarms
Battery Low
Webserver / Modbus
117
Input Bad
Webserver / Modbus
120
On Bypass
Webserver / Modbus
123
General Fault
Webserver / Modbus
132
Test In Progress
Webserver / Modbus
138
Shutdown imminent
Webserver / Modbus
137
Diagnose test failed
Webserver / Modbus
133
A P P EN D I X A