Section 7 I/O Displays
Smoothstart Start-up Sequence
3BUR002418-600 A
165
Smoothstart Start-up Sequence
Upon acquisition of an S100 I/O device, a diagnostic message identifying the device
will be issued to the user. Use the MOD Faceplate or Loop FCM Display to see the
following conditions:
•
For an analog I/O device, whether the CCF tag which references a channel has
an Output FCM in the Manual mode.
•
For a digital I/O device, whether the CCF device loop which references a
channel has NO COMMAND as its DEV_CMND attribute.
Upon acquisition the user must:
1.
Acknowledge a device acquisition diagnostic message.
2.
Call up the corresponding MOD Faceplate or Loop FCM Display to find out
what loops are affected.
3.
Make any necessary modifications to synchronize the control system with the
current outputs.
4.
Commission any affected CCF output FCMs by setting their output modes to
AUTO.
5.
Commission any affected CCF Device loops by issuing device commands as
required.
S100 Warmstart
Actions Upon Node Startup
Upon node startup, outputs to all devices are disabled. The database is downloaded
with each CCF loop output FCM in its initial output mode and each device loop
Value
The actual value of the input from the process or the output value
sent to the process.
For an output field, you can change the value of an output channel
by selecting it and entering a value.
Diagnostics
Not used.
See the S100 I/O instruction for error message information.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......