Delay Timer FCM
Appendix A Runtime Templates
268
3BUR002418-600 A
counting. You can compare the count to two configured reference values, or you can
initialize the count to a configured value.
TIME UNITS (SECONDS) Field
This field provides a means to scale the result into the desired time units. The result
is usually calculated in seconds. If this is appropriate for the application, leave this
field at its default value, 1. If another time unit is required, enter the value in this
field. The internal result value (in milliseconds) is converted to seconds and then
divided by the entry to become the final result of the FCM. For example, to specify
minutes, enter 60. To specify hours, enter 3600. Valid entry is a decimal number
greater than 0.
LOWER TIME LIMIT Field
This field specifies a reference value that the count is compared to. When the count
is less than the value in this field, the data base flag TIM_EXP1 is 0. When the
count is greater than or equal to the value in this field, TIM_EXP1 is set to 1. Valid
entry is a decimal number greater than or equal to 0.
HIGHER TIME LIMIT Field
This field specifies a reference value that the count is compared to. When the count
is less than the value in this field, the data base flag TIM_EXP2 is 0. When the
count is greater than or equal to the value in this field, TIM_EXP2 is set to 1. When
TIM_EXP2 is 1, the count is frozen at its current value and does not increment on
subsequent loop scans. Valid entry is a decimal number greater than or equal to 0.
Delay Timer FCM
This is a delay timer whose result is ON or OFF. There is one input to the Delay
Timer FCM whose value is also ON or OFF. Two timers are present in the
algorithm. One is related to the time that the input is in the ON state. The other is
related to the time the input is in the OFF state.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......