background image

 

Safety 

 

 

 

 

 

 

 

 

 

  

2CKA001473B5394

 

│5  

 

 

2.1 

Intended use 

The Smart Edge Gateway BECL/D.200.16 serves as protected, local network node between 
bus system, such as BACnet, Modbus or KNX and the IP building network.  

The device embeds openBOS

®

, the ABB operating system for Smart Buildings: a software 

platform that establishes the link between any connected equipment of a building and any 
software applications that will be used by building managers and/or building occupants.

 

Building edge connects any device of any brand having open and interoperable IP protocol such 
as Modbus, KNX, BACnet and MQTT. It includes an embedded Edge Editor Tool to create the 
database of your multiprotocol site. 

The BECL/D.200.16 also serves as access point for Cloud platform ABB Ability

TM

 as well as 

Clouds of third-party suppliers via openBOS as a Service (oBaaS).  

The BECL/D.200.16 is a modular DIN-Rail component (MDRC) in Pro 

M

-Design. The device is 

intended for mounting in installation distributors on 35 mm mounting rails. 

The intended use also includes adherence to all specifications in this manual. 

 

2.2 

Improper use 

Each use not listed in Chapter 2.1 

“Intended use“ on page 5 is deemed improper use and can 

lead to personal injury and damage to property. 

ABB is not liable for damages caused by use deemed contrary to the intended use of the 
device. The associated risk is borne exclusively by the user or operator. 

The device is not intended for the following: 

 

Unauthorized structural changes 

 

Repairs 

 

Outdoor use 

 

Use in bathroom areas 

 

2.3 

Target group / Qualifications of personnel 

Installation, commissioning and maintenance of the device must only be carried out by trained 
and properly qualified installer or system integrator. 

The installer or system integrator must have read and understood the manual and follow the 
instructions provided. 

The installer or system integrator must adhere to the valid national regulations in his/her country 
governing the installation, functional test, repair and maintenance of electrical products. 

The installer or system integrator must be familiar with and correctly apply the "five safety rules" 
(DIN VDE 0105, EN 50110): 

1.  Disconnect 

2.  Secure against being re-connected 

3.  Ensure there is no voltage 

4.  Connect to earth and short-circuit 

5.  Cover or barricade adjacent live parts; 

 

 

 

Summary of Contents for Ability BECL/D.200.16

Page 1: ...Product Manual 13 02 2023 V 1 5 ABB AbilityTM BECL D 200 16 Building Edge Control Brandi ng Rel ease 2018 01 01 ...

Page 2: ...ty 7 2 4 2 Anti Malware Software 8 2 5 Safety instructions 9 3 Information on protection of the environment 10 3 1 Environment 10 4 Product description 11 4 1 Scope of delivery 11 4 2 Device overview 12 4 3 Functions 13 4 3 1 Description of functions 13 4 4 LED Functions 15 5 Technical data 16 5 1 Dimensional drawings 18 6 Connection installation mounting 19 6 1 Safety instructions 19 6 2 Mounting...

Page 3: ...place ABB accepts no liability for errors and safety problems due the failure to observe the manual If you require additional information or have questions about the Building Ecosystem and its applications please contact ABB or visit our Internet site at https buildings ability abb Notice Depending on the user rights system configuration and equipment certain functions and settings cannot be made ...

Page 4: ...ion with the signal word Danger indicates an imminently threatening danger which leads to death or serious irreversible injuries Warning Serious damage to health The respective warning symbol in connection with the signal word Warning indicates a threatening danger which can lead to death or serious irreversible injuries Caution Damage to health The respective warning symbol in connection with the...

Page 5: ...pecifications in this manual 2 2 Improper use Each use not listed in Chapter 2 1 Intended use on page 5 is deemed improper use and can lead to personal injury and damage to property ABB is not liable for damages caused by use deemed contrary to the intended use of the device The associated risk is borne exclusively by the user or operator The device is not intended for the following Unauthorized s...

Page 6: ... the building Bus cables in outdoor areas or in areas with limited protection represent an increased safety risk The physical access should be made exceptionally difficult IP Network The local network represents a sensitive component for secure communication That is why unauthorized access to the local network should be prevented The normal security mechanisms for IP networks are to be used e g Se...

Page 7: ... check these standard ports are used locally and update if any change Edge Editor embeds all the functions to perform these actions Port Service Purpose 80 TCP HTTP Communication via unencrypted web server disabled as standard There is the risk that third parties can read the transmitted data 443 TCP HTTPS Communication via encrypted web server 1883 TCP MQTT Communication with building fieldbus de...

Page 8: ...Tool McAfee https www mcafee com Microsoft Security Essentials https de wikipedia org wiki Microsoft_Security_Essentials Avira https www avira com Clamscan for Win Mac OS2 Linux systems https de wikipedia org wiki ClamAV Calmwin https de wikipedia org wiki ClamAV MetaDefender used by EPPC https www opswat com products metadefender AVG Anti Virus https www avg com ...

Page 9: ...tricians Disconnect the mains voltage before mounting or dismantling Never use the device with damaged connecting cables Do not open covers that are firmly bolted to the housing of the device Use the device only if it is in a technically faultless state Do not make changes to or perform repairs on the device its components or its accessories Keep the device away from water and wet surroundings Att...

Page 10: ...e device at the appropriate collecting facility All packaging materials and devices bear the markings and test seals for proper disposal Always dispose of the packing materials and electric devices or their components via an authorized collection facility or disposal company The products meet the legal requirements in particular the laws governing electronic and electrical devices and the REACH or...

Page 11: ...unting rails To operate the device requires a supply voltage US 9 14 V DC which is supplied via an external SELV power adapter The device can be configured after the direct current supply and at least one LAN cable is connected 4 1 Scope of delivery Included in the scope of delivery are MDRC device 4 MW Connecting terminal for the power supply The power adapter for the power supply 12 V DC SELV mu...

Page 12: ...overview Fig 2 Overview of devices 1 Label holder 2 Connection of supply voltage US 3 Micro SD card slot 4 LAN 1 connection Ethernet 5 LAN 2 connection Ethernet 6 LED ON green 7 LED LAN Link yellow 8 LED status yellow 9 Reset button behind label holder ...

Page 13: ... protocol such as KNX net IP BACnet IP Modbus TCP IP or MQTT Compatible with all above protocols and manages these protocols as a data server Manages schedules alarms and saves trend logs independent of protocol Includes the openBOS operating system and organizes information in a building ontology based on rooms and zones offers a REST JSON API of the entire function openBOS as a Service oBaaS via...

Page 14: ... ontology Ontology is Combining data from one or several middleware levels Consolidation of data in a structured information model that is designated as ontology of the building This part is the central repository for the information A site is composed of several buildings Each building has roof s floor s facades parking s basements Define the description of the assets in the building the lamps th...

Page 15: ... LAN LINK Yellow Display of network connection Off when there is no network connection or no LAN port is connected with an IP router switch Lights up permanently when the device is ready for operation and when at least one LAN port is connected with an IP router switch Flickers during traffic on the LAN ports On when resetting the device Flashes when the IP address is reset 3 Hz Flashes when reset...

Page 16: ...AN connections Ethernet LAN 1 connection LAN 2 connection 10 100 1 000 BaseT IEEE 802 3 via RJ45 plug 10 100 BaseT IEEE 802 3 via RJ45 plug Number 2 Cable type Shielded network cable at least CAT 5e S UTP F UTP Micro SD card reader Card types Up to 2 TB microSD microSDHC microSDXC memory card not included in the scope of delivery Design Dimensions 3 54 2 76 25 inch H B D 90 70 63 5 mm H B D Housin...

Page 17: ...tion approval Protection type IP20 Mode of operation Type 1 IEC 60730 Approvals UL listed CDN US UL 60730 1 Automatic electric regulating and control devices reference number E499524 CE conformity according to EC guidelines Table 1 Technical data ...

Page 18: ...Technical data 2CKA001473B5394 18 5 1 Dimensional drawings Fig 3 Dimensional drawing all dimensions are in millimeters ...

Page 19: ...ice only if you have the necessary electrical engineering knowledge and experience Incorrect installation endangers your life and that of the user of the electrical system Incorrect installation can cause serious damage to property e g due to fire The minimum necessary expert knowledge and requirements for the installation are as follows Apply the five safety rules DIN VDE 0105 EN 50110 1 Disconne...

Page 20: ...DIN 60715 TH 35 including industrial version Installation To install the device perform the following steps Latch the modular DIN rail component onto the mounting rail Fig 4 Installation on mounting rails Dismantling To dismantle the device perform the following steps Press the device down 1 and then fold it toward the front 2 Fig 5 Removal from the mounting rails ...

Page 21: ...r adaptor necessary LAN 1 LAN 2 Connection to the IP network via Twisted Pair cable with RJ45 plug Connection to a standard IP switch or router of the building Communication with the field devices via BACnet or modbus Makes Cloud communication possible where the interface is available Notice The terminal designation is located on the housing Fig 7 Skinning length Skinning length 8 mm ...

Page 22: ...aintenance free In case of damage e g during transport or storage do not perform repairs Once the device is opened the warranty is void Access to the device must be guaranteed for operation testing inspection maintenance and repairs according to DIN VDE 0100 520 ...

Page 23: ...Notes 2CKA001473B5394 23 8 Notes ...

Page 24: ...nvironment 10 F Functions 13 I Improper use 5 Information on protection of the environment 10 Intended use 5 L LED Functions 15 Liability 3 4 M Maintenance 22 Mounting 20 N Notes 23 notes on the instruction manual 3 P Ports and services for supporting the main functionality 7 Product description 11 Q Qualification of the staff 5 S Safety 4 Safety instructions 9 19 Scope of delivery 11 T Target gro...

Page 25: ...us sbs insidesales abb com Technical Support Phone 1 877 226 7767 Hours 8 30 am to 5 00 pm ET Monday to Friday us sbs support abb com Postal address ABB Inc 2018 Powers Ferry Road Atlanta GA 30339 USA new abb com buildings Copyright 2023 ABB Inc All rights reserved 2CKA001473B5394 ...

Reviews: