MBP cable type and speed
Section 2 Transmission Technology
34
3BDS009029R5001 B
The bus trunk cable has a passive line terminator at each end.
Table 4. Basic data for the PROFIBUS PA reference cable
Parameter
PA, Cable type A
Cable design
shielded twisted pair
Conductor cross section (nominal)
0,8 mm²
Loop resistor (direct current)
44 Ohm/km
Wave resistance at 31,25 kHz
100 Ohm +20%
Wave attenuation at 39 kHz
3 dB/km
Capacitive asymmetry
2 nF/km
Group runtime distortion (7,9 ... 39) kHz 1,7 µs
Covering level of the shield
90%
The Power Link Modules of the PROFIBUS Linking Device LD 800P possess an
integrated bus terminator, which terminates the PROFIBUS PA line unilaterally
and therefore eliminates the need for a separate bus terminator on the Power Link
Modules. (see also