Technical Data
Appendix A Hardware Units
142
3BSE 027 941 R301
Modem support
Yes
COM4 Serial Communication
Communication speed
9600 baud
Signal levels
RS232-C
Connector
RJ45
Modem support
No
Electrical ModuleBus
I/O capacity
1 x S800 I/O base cluster with up to 12 x S800 I/O units.
Supply current
•
Max 24 V – 1.0 A (short circuit proof, fuse 2A fast)
•
Max 5 V – 1.5 A (short circuit proof)
Supply voltage variation 24 V – follows the input power at L+
Optical ModuleBus
I/O capacity
up to 7 x S800 I/O clusters each with 12 units
Connector
•
Duplex Fiber Optic Cable
•
Simplex Fiber Optic Cable
CEX-bus
Capacity
up to 12 communication interfaces
Supply current
Max 24 V – 2.4 A (fuse 3.15 A fast)
Table 32. PM856/PM860 and TP830 Interfaces – Technical data (Continued)
Item
Value
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......