TC562 Modem Unit – (Westermo MD-12DC)
Appendix A Hardware Units
192
3BSE 027 941 R301
cable resistance and capacitance. ABB recommends a minimum cable gauge of
0.2mm
2
with a capacitance of 40-80pF/m within an industrial environment.
For an office environment, ABB recommends a minimum cable gauge of 0.14mm
2
,
and a capacitance of 40-100pF/m. Use a shielded cable in a heavy industrial
environment and an unshielded cable in an office environment. A shielded cable is
often given a higher capacitance and will therefore provide a higher data
transmission speed.
Technical Data
Table 58. TC562 – Technical Data
Type
TC562 – Short Distance Modem
Manufacturer – Westermo – MD-12DC
Transfer
Asynchronous, full/half duplex/simplex
Power Supply
24 V DC (Min. 12 V DC – Max 36 V DC)
Power Consumption
3 W
Dimensions
55 x 100 x 128mm (2.2 x 3.9 x 5.0 in.)
Weight
400 g (0.9 lb)
Table 59. Transfer Distance (Cable 0.3 mm
2
/42 pF/m)
Meters (yd.)
bit/s
1000 ( 1094)
19200
2500 ( 2734)
9600
5000 ( 5468)
4800
8000 ( 8749)
2400
12000 (13123)
1200
18000 (19685)
600
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......