Section 1 Introduction
PM8xx/TP830 Processor Unit – General
3BSE 027 941 R301
35
Figure 6. Example of AC 800M/S800 I/O Interconnection in Single CPU Configuration
Max 12 units per cluster
DI810
AI810
DO810
PM8XX
CPU
CI852
Fieldbus H1
CI851
Max 12 units per cluster
TB820
DI810
AI810
AO820
To 6 Additional Optical
Electrical ModuleBus cluster
Max 12 units per cluster
ModuleBus clusters
CI830
TB820 DI810
AI810
AO820
See
See Note 3
Note 1
See
Note 2
Additional stations
up to a maximum of
32 stations per Segment
Note 1 – Maximum 7 clusters. Max 200 m between clusters.
Note 2 – Central S800 I/O. Maximum 96 units.
Note 3 – Remote S800 I/O. Maximum 24 units/station,
24 x 32 = 768 units per segment.
Repeater Unit
R
1 Segment of
PROFIBUS DP
Optical
Optical
Optical
FOUNDATION
Max 12 units
DI810
AI810
AO820
PROFIBUS DP
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......