Section 2 Installation
Installing the PROFIBUS DP Interface, CI851/TP851
3BSE 027 941 R301
67
Installing the PROFIBUS DP Interface, CI851/TP851
The CI851 is powered from the processor unit via the CEX-bus and requires
therefore no additional external power source.
Use the following procedure to install the CI851/TP851:
1.
Mount the unit onto the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
on page 49 and
Installing the PM8xx/TP830 Processor Unit in Single
2.
Install a connector on the PROFIBUS DP cable. Connect the cable screen to
the ground terminal within the connector to ground the screen via CI581.
A connector with a switchable built-in bus termination is recommended.
3.
Connect the PROFIBUS DP cable to the contact on the baseplate.
4.
If this is at the end of the PROFIBUS DP cable, switch the bus termination ON.
Otherwise leave the bus termination switched OFF.
PROFIBUS DP Connection
The PROFIBUS DP cable is connected via the 9-pin female D-type connector
located on TP851.
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......