Section 2 Installation
Installing the RS232-C Interface, CI853/TP853
3BSE 027 941 R301
71
Installing the RS232-C Interface, CI853/TP853
CI853 is powered from the processor unit via the CEX bus and requires therefore no
additional external power source.
Use the following procedure to install the CI853/TP853:
1.
Mount the unit onto the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
on page 49 and
Installing the PM8xx/TP830 Processor Unit in Single
2.
Connect the cable (maximum 15 m [16.4 yd}) to one of the contacts on the
baseplate. Connect the cable screen to the ground terminal within the connector
to ground the screen via CI583.
3.
If cables longer than 15 m (16.4 yd.) are required, then a short distance modem
TC562 must be used. In this case mount the modem onto a DIN-rail in a
suitable position, connect a 24 V DC power supply to the modem and connect
cable TK853 from CI853 to the TC562 modem input terminals
4.
Connect the TC562 modem output terminals to the outgoing cable.
The TC562 modem can be used for the following distances/speeds:
•
Up to 1000 m (1100 yd) with transmission speed 19200 bit/s
•
Up to 12000 m (13100 yd) with transmission speed 1200 bit/s
Connectors
Connect the RS232-C channels to the RJ45 connectors marked COM1 and COM2
on the TP853 Baseplate.
Table 12. CI853 RS23-C Interface – COM1 and COM2 Connectors
Pin
Designation
Direction
Description
1–9
–
–
See COM3 on TP830,
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......