Installing the INSUM Interface, CI857/TP853
Section 2 Installation
76
3BSE 027 941 R301
Installing the INSUM Interface, CI857/TP853
The CI857 is powered from the processor unit via the CEX-bus and requires
therefore no additional external power source.
Use the following procedure to install the CI857/TP853:
1.
Mount the unit onto the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
Installing the PM8xx/TP830 Processor Unit in Single
2.
Connect the Ethernet twisted pair cable to the COM1 connector on the
baseplate (COM2 is not used for connection to INSUM).
3.
Connect the other end of the Ethernet cable to the INSUM equipment via
Ethernet/LON Gateway.
Ethernet Twisted Pair Connection
The Ethernet twisted pair is connected via the 10 Base-T RJ45 connector located on
TP853. For a description of the connector see
Installing the CEX-bus
The CEX-bus, used for connection of communication interfaces to the processor
unit, is located on the left-hand side of the processor unit baseplate (TP830).
A bus termination unit must always be fitted to the last unit on the CEX-bus, as
shown in
on page 58. A TB850 male CEX-bus termination unit is
supplied with each PM8xx/TP830 processor unit.
However, should the configuration require the use of a TK850 extension cable, as
shown in
on page 59, then a TB851 female CEX-bus termination unit is
required and must be fitted to the last baseplate in the sequence. A TB851 female
CEX-bus termination unit is supplied with each TK850 extension cable.
TK850 CEX-bus Extension Cable
Only one TK850 CEX-bus extension cable may be used in any one CEX-bus. Cable
length: 0.7 m (2.3 in).
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......