CAUTION!
Risk of explosion!
Do not open, re-charge or disassemble a lithium battery. Attempts to charge
lithium batteries lead to overheating and possible explosions.
Protect them from heat and fire and store them in a dry place.
Never short-circuit or operate lithium batteries with the polarities reversed. The
batteries are likely to overheat and explode. Avoid chance short circuiting and
therefore do not store batteries in metal containers and do not place them on
metallic surfaces. Escaping lithium is a health hazard.
In order to prevent data losses or problems, the battery should be replaced after
3 years of utilisation or at least as soon as possible after receiving the "low
battery warning" indication.
Do not use a battery older than 3 years for replacement, do not keep batteries
too long in stock.
Parameter
Value
Nominal voltage
3 V
Nominal capacity
560 mAh
Temperature range (index below C0)
Operating: 0 °C...+60 °C
Storage: -20 °C...+60 °C
Transport: -20 °C...+60 °C
Temperature range (index C0 and above)
Operating: -40 °C...+70 °C
Storage: -40 °C...+85 °C
Transport: -40 °C...+85 °C
Battery lifetime
Typ. 3 years at 25 °C
Self-discharge
2 % per year at 25 °C
5 % per year at 40 °C
20 % per year at 60 °C
Protection against reverse polarity
Yes, by mechanical coding of the plug.
Insulation
The battery is completely insulated.
Connection
Red = positive pole = above at plug, black =
negative pole,
Weight
7 g
Dimensions
Diameter of the button cell: 24.5 mm
Thickness of the button cell: 5 mm
Part no.
Description
Product life cycle phase *)
1SAP 180 300 R0001
TA521, lithium battery
Active
Technical data
Ordering data
System assembly, construction and connection
AC500 (Standard) > Handling of accessories
2022/01/31
3ADR010278, 3, en_US
1017