NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist
environments.
Protect unused connectors and slots with TA535 protective caps for XC
devices.
Chapter 1.8.3.4 “TA535 - Protective caps for XC devices”
Table 209: Electromagnetic compatibility
Parameter
Value
Device suitable for:
Industrial applications
Yes
Domestic applications
No
Radiated emission (radio disturbances)
Yes, according to:
CISPR 16-2-3
Conducted emission (radio disturbances)
Yes, according to:
CISPR 16-2-1, CISPR
16-1-2
Electrostatic discharge (ESD)
Yes, according to:
IEC 61000-4-2, zone B,
criterion B
Fast transient interference voltages (burst)
Yes, according to:
IEC 61000-4-4, zone B,
criterion B
High energy transient interference voltages (surge)
Yes, according to:
IEC 61000-4-5, zone B,
criterion B
Influence of radiated disturbances
Yes, according to:
IEC 61000-4-3, zone B,
criterion A
Influence of line-conducted interferences
Yes, according to:
IEC 61000-4-6, zone B,
criterion A
Influence of power frequency magnetic fields
Yes, according to:
IEC 61000-4-8, zone B,
criterion A
In order to prevent malfunctions, it is recommended, that the operating per-
sonnel discharge themselves prior to touching communication connectors or
perform other suitable measures to reduce effects of electrostatic discharges.
System assembly, construction and connection
AC500-XC > System data AC500-XC
2022/01/31
3ADR010278, 3, en_US
1025