1.4.3.1.3 State LEDs
Table 56: Meaning of the diagnosis LEDs
LED
Color
State
Description
PWR
Green ON (light)
Power supply available
OFF (dark)
Power supply not available or defective
hardware
RDY
Yellow ON
Boot procedure
Blinking
Boot failure
OFF
---
RUN
Green ON
Communication module is operational
Blinking
---
OFF
Communication module is not operational
CAN-RUN Green ON
Operational: Device is in the
OPERATIONAL state
Single Flash
Stopped: Device is in STOPPED state
Blinking
Pre-operational: Device is in the
PREOPERATIONAL state
OFF
No communication or no power supply
CAN-ERR Red
ON
CANopen bus is off
Single flash
Warning limit reached: At least one of the
error counters of the CAN controller has
reached or exceeded the warning level
(too many error frames)
Double flash
Error control event: A guard event (NMT
Slave or NMTmaster) or a heartbeat event
(Heartbeat consumer) has occurred
OFF
No Error: Device is in working condition
CAN-RUN Yellow Blinking
(synchronously)
No production data available,
no bus communication possible.
CAN-ERR Yellow
LED state
during
firmware
update
CAN-RUN Green Blinking
(synchronously)
Firmware file transfers during
communication module firmware update.
CAN-ERR Red
CAN-RUN Green Blinking
(alternately)
Communication module writes the
firmware file to the internal flash.
Do not power off the PLC!
CAN-ERR Red
1.4.3.1.4 Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.