The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Number of I/O channels per module
Max. 24 (depending on the inserted communi-
cation interface module)
Distribution of the channels into groups
3 groups of max. 8 channels each (2.0...2.7,
3.0...3.7, 4.0...4.7), the allocation of the chan-
nels is given by the inserted communication
interface module
Network interface connector
10 screw or spring terminals (1.0...1.9)
Rated voltage
24 V DC
Max. permitted total current
10 A via the supply terminals (UP, UP3 and
ZP)
Grounding
Direct connection to the grounded DIN rail or
via the screws with wall mounting
Screw terminals
Front terminal, conductor connection vertically
with respect to the printed circuit board
Spring terminals
Front terminal, conductor connection vertically
with respect to the printed circuit board
Weight
200 g
Mounting position
Horizontal or vertical
1.5.3.2
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 211 400 R0001 TU517, terminal unit, 24 V DC, screw
terminals
Active
1SAP 211 200 R0001 TU518, terminal unit, 24 V DC, spring
terminals
Active
1SAP 411 200 R0001 TU518-XC, terminal unit, 24 V DC,
spring terminals, XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.5.4 TU531 and TU532 for I/O modules
● TU531, I/O terminal unit, 230 V AC, screw terminals
● TU532, I/O terminal unit, 230 V AC, spring terminals
● TU532-XC, I/O terminal unit, 230 V AC, spring terminals, XC version
● TU532-H, I/O terminal unit, hot swap, 230 V AC, spring terminals
● TU532-H-XC, I/O terminal unit, hot swap, 230 V AC, spring terminals, XC version
Device specifications
Terminal units (AC500 standard) > TU531 and TU532 for I/O modules
2022/01/31
3ADR010278, 3, en_US
135