Parameter
Value
Rated current (all channels together,
max.)
1.6 A
Lamp load (max.)
Not applicable
Max. leakage current with signal 0
< 0.5 mA
Output type
Non-protected
Protection type
External fuse on each channel
Rated protection fuse (for each channel)
1 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to
load specification
Switching frequency
With inductive loads
Max. 0.5 Hz
Short-circuit-proof / overload-proof
No
Overload message
No
Output current limitation
No
Resistance to feedback against 24 V DC
signals
Yes
Connection of 2 outputs in parallel
Not possible
Max. cable length
Shielded
500 m
Unshielded
150 m
Ordering data
Part no.
Description
Product life cycle phase *)
1TNE 968 902 R2001 DC561, digital input/output module,
16 configurable inputs/outputs,
transistor output, interfast connector
Classic
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.6.1.1.2 DC562 - Digital input/output module
● 16 configurable digital inputs/outputs in 1 group, 24 V DC
● Module-wise galvanically isolated
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
150