Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Galvanic isolation
Yes, between the input groups and the rest of
the module
Isolated groups
2 (8 channels per group)
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Ca. 10 mA
Max. power dissipation within the module
6 W
Weight
Ca. 222 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Technical data of the digital inputs
Parameter
Value
Number of channels per module
16 AC inputs (100-240 V AC)
Distribution of the channels into groups
2 (8 channels per group)
Input voltage range
0 V AC...264 V AC (47 Hz...63 Hz)
Input current per channel (typically at 25 °C)
< 3 mA (at 40 V AC)
> 6 mA (at 164 V AC)
> 8 mA (at 240 V AC)
Connections of the channels I0..I7
Terminals 1...8
Connections of the channels I8...I15
Terminals 10...17
Reference potential for the channels I0...I7
Terminal 9
Reference potential for the channels I8...I15
Terminal 18
Indication of the input signals
1 yellow LED per channel. The LED is on
when the input signal is high (signal 1).
Input type according to EN 61131-2
Type 1
Input signal range
Signal 0 (max.)
40 V AC
Undefined signal
40 V AC < U < 79 V AC
Signal 1 (min.)
79 V AC
Input delay
Signal 0 -> 1
Typ. 24 ms
Signal 1 -> 0
Typ. 24 ms
Input data length
2 bytes
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
192