Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage UP
Connections
Terminal 19 for UP (+24 V DC) and terminal
20 for ZP (0 V DC)
Rated value
24 V DC
Current consumption via UP terminal
5 mA + max. 0.5 A per output
Max. ripple
5 %
Inrush current
0.000002 A
2
s
Protection against reversed voltage
Yes
Rated protection fuse for UP
Recommended; the outputs must be pro-
tected by an 3 A fast-acting fuse
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Ca. 10 mA
Galvanic isolation
Yes, between the output group and the rest of
the module
Isolated groups
1 (8 channels per group)
Surge-voltage (max.)
35 V DC for 0.5 s
Power dissipation within the module (max.)
1.6 W
Weight
Ca. 115 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital outputs
Parameter
Value
Number of channels per module
8 transistor outputs (24 V DC, 0.5 A max.)
Distribution of the channels into groups
1 (8 channels per group)
Connection of the channels O0 to O7
Terminals 11 to 18
Common power supply voltage
Terminal 19 (positive pole of the process
voltage, signal name UP)
Reference potential for the channels O0 to O7
Terminal 20 (negative pole of the process
voltage, signal name ZP)
Indication of the output signals
1 yellow LED per channel; the LED is on
when the output signal is high (signal 1) and
the module is powered via the I/O bus
No effects of
multiple over-
loads