10
11
NO0
NO1
13 NO3
12 NO2
14 R0...3
15 NO4
16 NO5
17 NO6
18 NO7
19 R4...7
20 L+
120 VAC/
240 VAC
24 VAC/
~
~
L
N
L
N
120 VAC/
240 VAC
24 VAC/
Fig. 8: Connection of 24 V AC or 100-240 V AC actuators
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuit and overload.
–
Never short-circuit or overload the outputs.
–
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
–
Never connect voltages > 240 V. All outputs must be supplied from the
same phase.
–
Use an external 5 A fast protection fuse for the outputs.
24 VDC
–
+
CPU or
Bus Module
DO571
20
L+ / UP
I/O-Bus
M / ZP
L+
Fig. 9: Power supply - the negative connection is realized via the I/O bus
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
216