Parameter
Value
Relay output voltage
Rated value
24 V DC or 120/240 V AC
Output delay
Switching 0 to 1 (max.)
Typ. 10 ms
Switching 1 to 0 (max.)
Typ. 10 ms
Output data length
2 bytes
Output current
Rated current per channel (max.)
2.0 A (24 V DC / 24 V AC / 48 V AC /
120 V AC / 240 V AC, only resistive loads)
2.0 A (24 V AC / 48 V AC / 120 V AC, only
pilot duty)
1.5 A (240 V AC, only pilot duty)
Rated current per group (max.)
10 A
Lamp load (max.)
200 W (230 V AC), 30 W (24 V DC)
Spark suppression with inductive AC loads
Must be performed externally according to
driven load specification
Switching Frequencies
With resistive loads
Max. 1 Hz
With inductive loads
On Request
With lamp loads
Max. 1 Hz
Output type
Non-protected
Protection type
External fuse
1
)
Rated protection fuse
5 A fast
Short-circuit-proof / Overload-proof
No, should be provided by an external fuse
or circuit breaker
Overload message
No
Output current limitation
No
Connection of 2 outputs in parallel
Not possible
Lifetime of relay contacts (cycles)
100.000 at rated load
Max. cable length
Shielded
500 m
Unshielded
150 m
1
) Per group in case of group fuse protection. For each channel in case of channel-by-channel
fuse protection. The maximum current per group must not be exceeded.
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 231 300 R0000 DO573, digital output module, 16 DO,
relay output
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US