State LEDs
LED
State
Color
LED = OFF
LED = ON
Inputs I0...I7
Digital input Yellow
Input is OFF Input is ON
Outputs
O0...O7
Digital output Yellow
Output is
OFF
Output is ON
Technical data
The System Data of AC500-eCo apply
Chapter 2.5.1 “System data AC500-eCo V3”
Only additional details are therefore documented below.
Parameter
Value
Process supply voltage UP
Connections
Terminal 19 for UP (+24 V DC) and ter-
minal 20 for ZP (0 V DC)
Rated value
24 V DC
Current consumption via UP terminal
5 mA + max. 0.5 A per output
Max. ripple
5 %
Inrush current
0.000002 A
²
s
Protection against reversed voltage
Yes
Rated protection fuse for UP
Recommended; the outputs must be pro-
tected by an 3 A fast-acting fuse
Current consumption from 24 V DC power supply
at the L+/UP and M/ZP terminals of the CPU/com-
munication interface module
Ca. 10 mA
Galvanic isolation
Yes, between the input group and the
output group and the rest of the module
Isolated groups
2 groups (1 group for 8 input channels, 1
group for 8 output channels)
Surge-voltage (max.)
35 V DC for 0.5 s
Max. power dissipation within the module
2.3 W
Weight
ca. 120 g
Mounting position
Horizontal or vertical
Cooling
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
No effects of
multiple over-
loads
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
252