WARNING!
For screw terminals only: Danger of death by electric shock!
The IP 20 protection degree is only provided if all terminal screws are tightened.
Tighten all screws of unused load terminals of relay outputs if voltages > 24 V
are connected to the relay group.
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuit and overload.
–
Never short-circuit or overload the outputs.
–
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
–
Never connect voltages > 240 V. All outputs must be supplied from the
same phase.
–
Use an external 5 A fast protection fuse for the outputs.
The meaning of the LEDs is described in the Displays section
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Name
Value
Internal
Value
Internal
Value,
Type
Default
Min.
Max.
EDS Slot
Index
Module ID Internal
6140
1
)
WORD
6140
0x17FC
0
65535
xx01
Ignore
module
No
Yes
0
1
BYTE
No
(0x00)
Parameter
length
Internal
1
BYTE
0
0
255
xx02
2
)
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
263