Parameter
Value
With inductive loads
Max. 0.5 Hz
With lamp loads
Max. 11 Hz with max. 5 W
Short-circuit-proof / overload-proof
Yes
Overload message (I > 0.7 A)
Yes, after ca. 100 ms
Output current limitation
Yes, automatic reactivation after short cir-
cuit/overload
Resistance to feedback against 24 V signals Yes
Max. cable length
Shielded
1000 m
Unshielded
600 m
The following drawing shows the circuitry of a digital input/output with the varistors for demag-
netization when inductive loads are switched off.
UPx (+24 V)
Digital input/output
ZPx (0 V)
for demagnitization when inductive
loads are switched off
Technical data of the fast counter
The fast counter of the module does not work if the module is connected to a
–
FBP interface module
–
CS31 bus module
–
CANopen communication interface module
Parameter
Value
Used inputs
C24 / C25
Used outputs
C26
Counting frequency
Max. 50 kHz
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US