Parameter
Value
Process supply voltage UP
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP)
as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
From 24 V DC power supply at the
terminals UP/L+ and ZP/M of the CPU/
communication interface module
ca. 2 mA
From UP at normal operation / with out-
puts
0.05 A + output loads
Inrush current from UP (at power up)
0.010 A
²
s
Max. power dissipation within the module
6 W (outputs OFF)
Weight (without terminal unit)
ca. 300 g
Mounting position
Horizontal or vertical with derating (output
load reduced to 50 % at 40 °C per group)
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital inputs
Parameter
Value
Number of channels per module
8
Distribution of the channels into groups
1 group of 8 channels
Terminals of the channels I0 to I7
1.0 to 1.7
Reference potential for all inputs
Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of
the process supply voltage, signal name ZP)
Galvanic isolation
From the rest of the module (I/O bus)
Indication of the input signals
One yellow LED per channel, the LED is ON
when the input signal is high (signal 1)
Monitoring point of input indicator
LED is part of the input circuitry
Input type acc. to EN 61131-2
Type 1
No effects of
multiple over-
loads
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
336